2-6
IMSBR10-E1
When using internal reference junction compensation on the
thermocouple input, take measures to stabilize the temperature at the
input terminal.
• Always use the terminal cover.
• Do not use thick wires which may cause large heat dissipation (cross sectional area of 0.5 mm
2
or less
recommended).
• Make sure that the ambient temperature remains reasonably stable. Large temperature fluctuations can occur if
a nearby fan turns ON or OFF.
Connecting the input wires in parallel with other devices can cause signal
degradation, affecting all connected devices.
If you need to make a parallel connection, then
• Turn the burnout detection function OFF.
• Ground the instruments to the same point.
• Do not turn ON or OFF another instrument during operation. This can have adverse effects on the other
instruments.
• RTDs cannot be wired in parallel.
Arrangement of the Measuring Input Terminals
A terminal cover is screwed in place on the measuring input terminal block on the rear panel. A label indicating
the terminal arrangement is affixed to the cover.
Measuring input
terminal block
Terminal cover
attachment screws
Pen Model
+/A
–/B
b
+/A
–/B
b
Channel 1
Channel 2
Channel 3
Channel 4
Channel 1
Channel 3
Channel 2
Channel 4
+/A
–/B
b
Screw input terminal
Clamped input terminal
(/H2 option)
2.3 Input Signal Wiring