1-12
IMSBR10-E1
Non-Hold/Hold Operation of Alarm Output Relays
The alarm output relay can be set to operate in the following fashion when the alarm condition is no longer met.
• Turn off the relay output (non-hold).
• Hold the relay output until the alarm ACK operation is executed (hold).
The setting applies to all alarm output relays.
The default setting is non-hold.
Alarm
Alarm occurrence
Alarm release
Alarm output
relay
Alarm
ACK
Alarm
ACK
Alarm
ACK
or
or
Hold
Non-hold
Activated
Released
Note
• If the reflash alarm is enabled, I01 to I03 are fixed to non-hold operation. Specifying Hold produces no
effect.
• If diagnosis output is enabled, I01 is fixed to non-hold operation. Specifying Hold produces no effect.
<Related Topics>
Setting the non-hold/hold operation of alarm output relays: Section 7.1
Alarm ACK Operation
The alarm acknowledge (alarm ACK) operation releases all alarm indications and relay outputs (/A1, /A2, /A3, /
A4, and /A5 options) that are activated when the alarm indication or alarm output relay is set to hold operation.
This operation can be executed from the front panel key.
<Related Topics>
Alarm ACK operation: Section 3.12