1-10
IMSBR10-E1
Reflash Alarm
When multiple alarms are assigned to one alarm output relay, this function notifies the occurrence of subsequent
alarms after the relay is activated by the first alarm. When subsequent alarms occur, the output relay is released
temporarily (approximately 500 ms).
The reflash alarm function is set to three output relays (I01, I02, and I03 (I01 and I02 for the /A1 option)).
By default, the reflash alarm is disabled.
Alarm
Alarm output relay
(Reflash alarm ON)
Alarm output relay
(Reflash alarm OFF)
Channel 1
Channel 3
Channel 2
Approx. 500 ms Approx. 500 ms
Note
• If the reflash alarm is enabled, I01 to I03 are set to reflash alarm operation. In this case, I01 to I03 are set to
OR operation and non-hold operation regardless of the settings specified in “AND/OR Operation of Alarm
Output Relays” and “Non-Hold/Hold Operation of Alarm Output Relays” described below.
• If diagnosis output is enabled, I01 is set to diagnosis output.
<Related Topics>
Setting the reflash alarm: Section 7.1
1.3 Alarms