7. COMMUNICATION DATA LIST
IMR01Y36-E2
77
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
30
(0x001E)
Responsive action trigger
point for EDS
♣
64 R/W TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.0 to Input span (Unit: %)
TC/RTD:
1 (1.0)
V/I: 1.0
31
(0x001F)
Operation mode
assignment 1
(Logic output selection
function)
Logic output 1 to 4
64 R/W
0
32
(0x0020)
Operation mode
assignment 2
(Logic output selection
function)
Logic output 5 to 8
64 R/W
0: No assignment
1: Operation mode (monitor, control)
2: Operation mode
(monitor, event function, control)
3: Auto/Manual
4: Remote/Local
5: Unused (Do not set this one)
0
33
(0x0021)
SV select function
64 R/W 0: Remote SV function
1: Cascade control function
2: Ratio setting function
3: Cascade control 2 function
0
34
(0x0022)
Remote SV function
master channel module
address
64 R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
−
1
35
(0x0023)
Remote SV function
master channel selection
64
R/W 1 to 99
1
36
(0x0024)
Output distribution master
channel module address
64 R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
−
1
37
(0x0025)
Output distribution master
channel selection
64
R/W 1 to 99
1
38
(0x0026)
Address of interacting
modules
64 R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
−
1
39
(0x0027)
Channel selection of
interacting modules
64 R/W 1 to 99
Becomes validated when the selected module
is “Z-TIO module.”
1
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.