7. COMMUNICATION DATA LIST
IMR01Y36-E2
75
7.3 Z-TIO Module Extended Object (0x65: 65Hex)
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
1
(0x0001)
Comprehensive event state
64
RO Bit data
Bit 0: Event 1 state
Bit 1: Event 2 state
Bit 2: Event 3 state
Bit 3: Event 4 state
Bit 4: Heater break alarm state
Bit 5: Temperature rise completion
Bit 6: Burnout
Bit 7 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 127]
⎯
2
(0x0002)
Logic output monitor
Bit data
Bit 0: Logic output 1
Bit 1: Logic output 2
Bit 2: Logic output 3
Bit 3: Logic output 4
Bit 4: Logic output 5
Bit 5: Logic output 6
Bit 6: Logic output 7
Bit 7: Logic output 8
Bit 8 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 255]
⎯
3
(0x0003)
Output distribution
selection
64 R/W 0:
Control
output
1: Distribution output
0
4
(0x0004)
Output distribution bias
64
R/W
−
100.0 to
+
100.0 %
0.0
5
(0x0005)
Output distribution ratio
64
R/W
−
9.999 to
+
9.999
1.000
6
(0x0006)
Minimum ON/OFF time
of proportioning cycle
64
R/W 0 to 1000 ms
This item becomes RO (Only reading data is
possible) for the Voltage/Current output
specification.
0
7
(0x0007)
Area soak time stop
function
64
R/W 0: No function
1: Event 1
2: Event 2
3: Event 3
4: Event 4
0
8
(0x0008)
EDS mode
(for disturbance 1)
64 R/W
0
9
(0x0009)
EDS mode
(for disturbance 2)
64 R/W
0: No function
1: EDS function mode
2: Learning mode
3: Tuning mode
EDS function: External disturbance
suppression function
0
10
(0x000A)
EDS value 1
(for disturbance 1)
64
R/W
0.0
11
(0x000B)
EDS value 1
(for disturbance 2)
64
R/W
0.0
12
(0x000C)
EDS value 2
(for disturbance 1)
64
R/W
0.0
13
(0x000D)
EDS value 2
(for disturbance 2)
64 R/W
−
100.0 to
+
100.0 %
0.0
Continued on the next page.