7. COMMUNICATION DATA LIST
IMR01Y36-E2
53
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
46
(0x002E)
Proportional band
[heat-side]
★
♣
64 R/W TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool
actions in case of a Heat/Cool PID control
type.)
TC/RTD: 30
V/I: 30.0
47
(0x002F)
Integral time
[heat-side]
★
♣
64 R/W PID control or Heat/Cool PID control:
0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or
0.1 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
240
48
(0x0030)
Derivative time
[heat-side]
★
♣
64 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection
.
60
49
(0x0031)
Control response
parameter
★
♣
64 R/W 0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalidate.
PID control
,
Position
proportioning
control: 0
Heat/Cool PID
control: 2
50
(0x0032)
Proportional band
[cool-side]
★
♣
64 R/W TC/RTD inputs:
1 (0.1) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of Input span
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
TC/RTD: 30
V/I: 30.0
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.