6. DeviceNet COMMUNICATION
IMR01Y36-E2
40
Example of communication data list
This is a list of communication data items in the previous parameter setting example (P. 35).
(Communication data items IN and OUT corresponding to 21 words, respectively.)
•
Measured and setting data items from No. 1 to 5 (corresponding to 5 words) are those assign as fixed.
( section)
•
Communication items set on and after No. 6 are assigned by the specified number of
communication controllers.
•
Data of unused items become “0.”
No.
Measured data items (IN)
No.
Setting data items (OUT)
1
Receive counter
1
Setting state selection (All controller)
2
Alarm state (Controller 1 to 16)
2
Setting state selection (Controller 1 to 16)
3
Alarm state
(Controller 17 to 31, Setting update flag)
3
Setting state selection
(Controller 17 to 31, RUN/STOP)
4
RUN/STOP state (Controller 1 to 16)
4
RUN/STOP transfer (Controller 1 to 16)
5
RUN/STOP state (Controller 17 to 31)
5
RUN/STOP transfer (Controller 17 to 31)
6
Measured value (PV) [CH1 of controller 1]
6
Set value (SV) [CH1 of controller 1]
7
Measured value (PV) [CH2 of controller 1]
7
Set value (SV) [CH2 of controller 1]
8
Measured value (PV) [CH3 of controller 1]
8
Set value (SV) [CH3 of controller 1]
9
Measured value (PV) [CH4 of controller 1]
9
Set value (SV) [CH4 of controller 1]
10
Measured value (PV) [CH1 of controller 2]
10
Set value (SV) [CH1 of controller 2]
11
Measured value (PV) [CH2 of controller 2]
11
Set value (SV) [CH2 of controller 2]
12
Measured data is fixed in “0”
1
12
Setting data are invalidated
2
13
Measured data is fixed in “0”
1
13
Setting data are invalidated
2
14
Manipulated output value (MV) monitor [heat-side]
[CH1 of controller 1]
14
Event 1 set value [CH1 of controller 1]
15
Manipulated output value (MV) monitor [heat-side]
[CH2 of controller 1]
15
Event 1 set value [CH2 of controller 1]
16
Manipulated output value (MV) monitor [heat-side]
[CH3 of controller 1]
16
Event 1 set value [CH3 of controller 1]
17
Manipulated output value (MV) monitor [heat-side]
[CH4 of controller 1]
17
Event 1 set value [CH4 of controller 1]
18
Manipulated output value (MV) monitor [heat-side]
[CH1 of controller 2]
18
Event 1 set value [CH1 of controller 2]
19
Manipulated output value (MV) monitor [heat-side]
[CH2 of controller 2]
19
Event 1 set value [CH2 of controller 2]
20
Measured data is fixed in “0”
1
20
Setting data are invalidated
2
21
Measured data is fixed in “0”
1
21
Setting data are invalidated
2
1
Because controller 2 is 2-channel type, as for the measurement data, “0” becomes fixed.
2
Because controller 2 is 2-channel type, the setting data become invalidated.
For details of communication items, refer to
7. COMMUNICATION DATA LIST (P. 47)
.