7. COMMUNICATION DATA LIST
IMR01Y36-E2
52
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
34
(0x0022)
Auto/Manual transfer
64
R/W 0: Auto mode
1: Manual mode
0
35
(0x0023)
Remote/Local transfer
64
R/W 0: Local mode
1: Remote mode
When performing remote control by remote
setting input and also performing cascade
control and ratio setting, transfer to the
remote mode.
0
36
(0x0024)
RUN/STOP transfer
64
R/W 0: STOP mode (Control stop)
1: RUN mode (Control start)
0
37
(0x0025)
Memory area transfer
64
R/W 1 to 8
1
38
(0x0026)
Interlock release
64
R/W 0: Normal state
1: Interlock release execution
0
39
(0x0027)
Event 1 set value (EV1)
★
64 R/W
50
40
(0x0028)
Event 2 set value (EV2)
★
64 R/W
50
41
(0x0029)
Event 3 set value (EV3)
★
64 R/W
50
42
(0x002A)
Event 4 set value (EV4)
★
64 R/W
Deviation action, Deviation action
between channels, Temperature rise
completion range*:
−
Input span to +Input span
Process action, SV action:
Input scale low to Input scale high
MV action:
−
5.0 to +105.0 %
* When temperature rise completion is
selected at Event 3 action type.
If the Event type corresponds to “0: None,”
set to RO (Only reading data is possible).
If Event 4 corresponds to “9: Control loop
break alarm (LBA),” the Event 4 set value
becomes RO (Only reading data is
possible).
50
43
(0x002B)
Control loop break alarm
(LBA) time
★
64
R/W 0 to 7200 seconds (0: Unused)
480
44
(0x002C)
LBA deadband
★
64
R/W 0 (0.0) to Input span
0 (0.0)
45
(0x002D)
Set value (SV)
★
64
R/W Setting limiter low to Setting limiter high TC/RTD: 0
V/I: 0.0
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
Continued on the next page.