7. COMMUNICATION DATA LIST
IMR01Y36-E2
69
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
193
(0x00C1)
Integral time limiter (high)
[cool-side]
♣
64 R/W
3600
194
(0x00C2)
Integral time limiter (low)
[cool-side]
♣
64 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
0
195
(0x00C3)
Derivative time limiter
(high) [cool-side]
♣
64 R/W
3600
196
(0x00C4)
Derivative time limiter
(low) [cool-side]
♣
64 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
0
197
(0x00C5)
Open/Close output neutral
zone
♣
64
R/W 0.1 to 10.0 % of output
2.0
198
(0x00C6)
Unused
⎯
⎯
⎯
⎯
199
(0x00C7)
Action at feedback
resistance (FBR) input
break
♣
64 R/W 0: Action depending on the valve
action at STOP
1: Control action continued
0
200
(0x00C8)
Feedback adjustment
♣
64
R/W 0: Adjustment end
1: During adjustment on the open-side
2: During adjustment on the close-side
⎯
201
(0x00C9)
Control motor time
♣
64
R/W 5 to 1000 seconds
10
202
(0x00CA)
Integrated output limiter
♣
64 R/W 0.0 to 200.0 % of control motor time
(0.0: OFF)
Becomes invalidated when there is
Feedback resistance (FBR) input.
150.0
203
(0x00CB)
Valve action at STOP
♣
64
R/W 0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
Becomes validated when there is no
Feedback resistance (FBR) input or the
Feedback resistance (FBR) input is
disconnected.
0
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.