7. COMMUNICATION DATA LIST
IMR01Y36-E2
73
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
234
(0x00EA)
RUN/STOP
1
2
R/W Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data RUN/STOP state is depending on
the value of RUN/STOP logic
selection (ID: 242)
•
ID: 242
=
0
0: RUN (control start)
1: STOP (control stop)
•
ID: 242
=
1
0: STOP (control stop)
1: RUN (control start)
[Decimal number: 0 to 65535]
Link RUN/STOP transfer (ID: 36)
0
235
(0x00EB)
Setting update flag
1
1
RO 0: Setting update is completed
1: During setting update
⎯
ID236, ID237 are communication environment setting data.
236
(0x00EC)
Number of Polling I/O
communication
controllers
1
1
R/W 1 to 31
10
237
(0x00ED)
Unused
⎯
⎯
⎯
⎯
ID238 is normal setting data.
238
(0x00EE)
COM-JH error code
1
1
RO Bit data
Bit 0: Back-up error
Bit 1: Controller communication error
Bit 2 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 3]
⎯
After ID239 are communication environment setting data.
239
(0x00EF)
Number of connected
controller in Controller
communication
1
1
RO 0 to 31
⎯
240
(0x00F0)
Number of communication
measured data items (IN)
when conducting Polling
I/O communication
1, 2
1
R/W 0: Based on the DIP switch setting
1 to 5:
5 words
6 to 200: 6 to 200 words
0
241
(0x00F1)
Number of communication
setting data items (OUT)
when conducting Polling
I/O communication
1, 2
1
R/W 0: Based on the DIP switch setting
1 to 5:
5 words
6 to 200: 6 to 200 words
0
1
Validate only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned on again.
: It is possible to set in the communication environment setting by the rotary switch of COM-JH (Refer
to P. 23) or configuration tool (Refer to P. 33).
Continued on the next page.