7. COMMUNICATION DATA LIST
IMR01Y36-E2
63
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
130
(0x0082)
Event 3 delay timer
64
R/W 0 to 18000 seconds
If Event 3 corresponds to “9: Temperature
rise completion,” the Event 3 delay timer
becomes the Temperature rise completion
soak time.
0
131
(0x0083)
Force ON of Event 3
action
64 R/W Bit
data
Bit 0: Event output turned on at input
error occurrence
Bit 1: Event output turned on in Manual
mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the
Setting change rate limiter is being
operated
Bit 4 to Bit 15: Unused
Data 0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
132
(0x0084)
Event 4 type
64
R/W 0: None
1: Deviation high
(SV monitor value used)
1
2: Deviation low
(SV monitor value used)
1
3: Deviation high/low
(SV monitor value used)
1
4: Band (SV monitor value used)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Control loop break alarm (LBA)
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high
(Local SV value used)
1
15: Deviation low
(Local SV value used)
1
16: Deviation high/low
(Local SV value used)
1
17: Deviation (Local SV value used)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels
high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
Based on
model code.
When not
specifying: 0
Continued on the next page.