8. USAGE EXAMPLE
IMR01Y35-E3
62
8.3 Use Instruments Setting
Set the COM-JG and controller (SRZ) as the following.
There is not the hardware setting of PLC: SIMATIC S7-300 series (SIEMENS AG).
COM-JG setting
Set COM-JG to the following conditions.
•
PROFIBUS address:
1
•
Controller communication speed: 19200 bps (Factory set value)
For setting procedure, refer to
5. SETTING (P. 15)
.
Controller (SRZ) setting
•
Module address:
Z-TIO module: 4-channel type: 1, 2
2-channel type: 3
Z-DIO
module:
17
The module address of a Z-TIO module will be the value
(decimal) set in the address setting switch plus “1.”
The module address of a Z-DIO module will be the value
(decimal) set in the address setting switch plus “17.”
•
Communication protocol: Modbus-RTU
•
Communication speed:
19200 bps (Factory set value)
•
Data bit configuration:
Data 8-bit, Without parity bit, Stop 1-bit
For setting method, refer to
Z-TIO Host Communication Quick Instruction Manual
(IMS01T02-E )
or
Z-DIO INSTRUCTION MANUAL (IMS01T03-E )
.