7. COMMUNICATION DATA MAP
52
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
14
Integral time [cool-side]
CH1
CH2
CH3
CH4
0534
0535
0536
0357
1332
1333
1334
1335
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
240
15 Derivative
time
[cool-side]
CH1
CH2
CH3
CH4
0538
0539
053A
053B
1336
1337
1338
1339
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
60
16 Overlap/Deadband
CH1
CH2
CH3
CH4
053C
053D
053E
053F
1340
1341
1342
1343
R/W
TC/RTD inputs:
−
Input span to +Input span (Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
−
100.0 to
+
100.0 % of Input span
0
17 Manual
reset
CH1
CH2
CH3
CH4
0540
0541
0542
0543
1344
1345
1346
1347
R/W
−
100.0 to
+
100.0 %
0.0
18
Setting change rate limiter
(up)
CH1
CH2
CH3
CH4
0544
0545
0546
0547
1348
1349
1350
1351
R/W
0 (0.0) to Input span/unit time *
0 (0.0): Unused
0 (0.0)
19
Setting change rate limiter
(down)
CH1
CH2
CH3
CH4
0548
0549
054A
054B
1352
1353
1354
1355
R/W
* Unit time: 60 seconds (factory set value)
0 (0.0)
20
Area soak time
CH1
CH2
CH3
CH4
054C
054D
054E
054F
1356
1357
1358
1359
R/W
0 minutes 00 seconds to 199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to 99 hours 59 minutes:
0 to 5999 minutes
0
21
Link area number
CH1
CH2
CH3
CH4
0550
0551
0552
0553
1360
1361
1362
1363
R/W
0 to 8
(0: No link)
0