7. COMMUNICATION DATA MAP
IMR01Y35-E3
47
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
165 Integral time limiter (high)
[heat-side]
♣
CH1
CH2
CH3
CH4
02B6
02B7
02B8
02B9
694
695
696
697
R/W
3600
166 Integral time limiter (low)
[heat-side]
♣
CH1
CH2
CH3
CH4
02BA
02BB
02BC
02BD
698
699
700
701
R/W
PID control or Heat/Cool PID control:
0 to 3600 seconds or 0.0 to 1999.9 seconds
Position proportioning control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the Integral/Derivative
time decimal point position selection.
PID control,
Heat/Cool PID
control: 0
Position
proportioning
control: 1
167 Derivative time limiter
(high) [heat-side]
♣
CH1
CH2
CH3
CH4
02BE
02BF
02C0
02C1
702
703
704
705
R/W
3600
168 Derivative time limiter
(low) [heat-side]
♣
CH1
CH2
CH3
CH4
02C2
02C3
02C4
02C5
706
707
708
709
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the Integral/Derivative
time decimal point position selection.
0
169 Proportional band limiter
(high) [cool-side]
♣
CH1
Unused
CH3
Unused
02C6
Unused
02C8
Unused
710
Unused
712
Unused
R/W
TC/RTD:
Input span
V/I: 1000.0
170 Proportional band limiter
(low) [cool-side]
♣
CH1
Unused
CH3
Unused
02CA
Unused
02CC
Unused
714
Unused
716
Unused
R/W
TC/RTD inputs:
1 to input span or 0.1 to input span
(Unit:
°
C [
°
F])
Varies with the setting of the Decimal point
position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
TC/RTD:
1 (0.1)
V/I: 0.1
171 Integral time limiter (high)
[cool-side]
♣
CH1
Unused
CH3
Unused
02CE
Unused
02D0
Unused
718
Unused
720
Unused
R/W
3600
172 Integral time limiter (low)
[cool-side]
♣
CH1
Unused
CH3
Unused
02D2
Unused
02D4
Unused
722
Unused
724
Unused
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the Integral/Derivative
time decimal point position selection.
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
0
173 Derivative time limiter
(high) [cool-side]
♣
CH1
Unused
CH3
Unused
02D6
Unused
02D8
Unused
726
Unused
728
Unused
R/W
3600
174 Derivative time limiter
(low) [cool-side]
♣
CH1
Unused
CH3
Unused
02DA
Unused
02DC
Unused
730
Unused
732
Unused
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point position
selection.
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
0
175 Open/Close output neutral
zone
♣
CH1
Unused
CH3
Unused
02DE
Unused
02E0
Unused
734
Unused
736
Unused
R/W
0.1 to 10.0 %
2.0
176 Action at feedback
resistance (FBR) input
error
♣
CH1
Unused
CH3
Unused
02E2
Unused
02E4
Unused
738
Unused
740
Unused
R/W
0: Action depending on the valve action at
STOP
1: Control action continued
0
177 Feedback
adjustment
♣
CH1
Unused
CH3
Unused
02E6
Unused
02E8
Unused
742
Unused
744
Unused
R/W
0: Adjustment
end
1: During adjustment on the open-side
2: During adjustment on the close-side
⎯
178 Control motor time
♣
CH1
Unused
CH3
Unused
02EA
Unused
02EC
Unused
746
Unused
748
Unused
R/W
5 to 1000 seconds
10
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.