7. COMMUNICATION DATA MAP
56
IMR01Y35-E3
z
DI assignment table
Set
value
DI1 DI2 DI3 DI4
DI5
DI6
DI7 DI8
0
No assignment
1
AUTO/MAN
4
2
REM/LOC
4
3
Interlock release
EDS start signal 1
4
Soak
stop
5
RUN/STOP
4
6
REM/LOC
4
7
AUTO/MAN
4
EDS start signal 1
8
Operation
mode
3
Soak
stop
9
RUN/STOP
4
10
EDS start signal 1
11
REM/LOC
4
Soak
stop
12
RUN/STOP
4
13
Area set
2
Soak
stop
14
EDS start signal 1
15
Soak
stop
RUN/STOP
4
16
EDS start signal 1
17
REM/LOC
4
Soak
stop
18
Interlock
release
AUTO/MAN
4
RUN/STOP
4
19
Soak
stop
20
EDS start signal 1
RUN/STOP
4
21
Soak
stop
22
Soak
stop
23
AUTO/MAN
REM/LOC
EDS start signal 1
24
RUN/STOP
4
25
Memory area transfer (1 to 8)
1
REM/LOC
EDS start signal 1
Soak stop
26 Memory
area
transfer (1, 2)
1
Area set
2
Interlock
release
RUN/STOP
4
AUTO/MAN
4
REM/LOC
4
Operation mode
3
27
Memory area transfer (1 to 8)
1
Area
set
2
Operation
mode
3
28 Memory
area
transfer (1, 2)
1
Area set
2
EDS start signal 1
EDS start signal 2
29
EDS start signal 1
EDS start signal 2
Interlock release
RUN/STOP
4
AUTO/MAN
4
REM/LOC
4
Operation mode
3
RUN/STOP: RUN/STOP transfer (Contact closed: RUN)
AUTO/MAN: Auto/Manual transfer (Contact closed: Manual mode)
REM/LOC: Remote/Local transfer (Contact closed: Remote mode)
Interlock release (Contact closed: Interlock release)
EDS start signal 1 (Contact closed: EDS start signal ON [for disturbance 1])
EDS start signal 2 (Contact closed: EDS start signal ON [for disturbance 2])
Soak stop (Contact closed: Soak stop)
1
Memory area transfer
(
×
:Contact open
−
: Contact closed)
Memory area number
1 2 3 4 5 6 7 8
DI1
×
−
×
−
×
−
×
−
DI2
×
×
−
−
×
×
−
−
DI3
×
×
×
×
−
−
−
−
2
Area set becomes invalidate prior to factory shipment.
3
Operation mode transfer
(
×
:Contact open
−
: Contact closed)
Operation mode
Unused Monitor
Monitor
+
Event function
Control
DI5 (DI7)
×
−
×
−
DI6 (DI8)
×
×
−
−
4
Actual device states (AUTO/MAN, REM/LOC, RUN/STOP)
DI-switched
state
Communication-switched state
Actual device state
Manual
→
Auto
Manual (Contact closed)
Auto
→
Manual
Manual mode
Manual
→
Auto
Auto/Manual transfer
a
(AUTO/MAN)
Auto (Contact open)
Auto
→
Manual
Auto mode
Remote
→
Local
Remote/Local transfer
a
Remote (Contact closed)
Local
→
Remote
Remote mode
(REM/LOC)
Remote
→
Local
Local (Contact open)
Local
→
Remote
Local mode
STOP
→
RUN
RUN
RUN (Contact closed)
RUN
→
STOP
STOP
RUN/STOP
b
STOP (Contact open)
STOP
→
RUN
STOP
a
Device state when AUTO/MAN or REM/LOC assigned to DI is set so that the Z-TIO module and Z-DIO module are linked using the Master-slave mode of
the Z-TIO module.
b
STOP of RUN/STOP switching is given priority regardless of communication or DI switching.
Contact closed
Contact open
250 ms or more
DI signal will become validate at rising edge after the closed contact is held for 250ms.
(Rising edge)