7. COMMUNICATION DATA MAP
50
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
203 Address of interacting
modules
CH1
CH2
CH3
CH4
034E
034F
0350
0351
846
847
848
849
R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
−
1
204 Channel selection of
interacting modules
CH1
CH2
CH3
CH4
0352
0353
0354
0355
850
851
852
853
R/W
1 to 99
Becomes validated when the selected module
is “Z-TIO module”.
1
205 Selection switch of
interacting modules
CH1
CH2
CH3
CH4
0356
0357
0358
0359
854
855
856
857
R/W
Bit data
Bit 0: Memory area number
Bit 1: Operation mode
Bit 2: Auto/Manual
Bit 3: Remote/Local
Bit 4: EDS start signal
Bit 5: Interlock release
Bit 6: Suspension of area soak time
Bit 7 to Bit 15: Unused
Data 0:
No
interaction
1: Interact with other channels
[Decimal number: 0 to 127]
0
206 Control
RUN/STOP
holding setting
⎯
035A 858
R/W
0: Not holding (STOP start)
1: Holding (RUN/STOP hold)
1
207 Interval
time
⎯
035B
859
R/W
0 to 250 ms
10