7. COMMUNICATION DATA MAP
IMR01Y35-E3
31
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
9
Remote setting (RS) input
value monitor
CH1
CH2
CH3
CH4
001D
001E
001F
0020
29
30
31
32
RO
Setting limiter low to Setting limiter high
⎯
10
Burnout state monitor
CH1
CH2
CH3
CH4
0021
0022
0023
0024
33
34
35
36
RO
0: OFF
1: ON
⎯
11
Event 1 state monitor
CH1
CH2
CH3
CH4
0025
0026
0027
0028
37
38
39
40
RO
⎯
12
Event 2 state monitor
CH1
CH2
CH3
CH4
0029
002A
002B
002C
41
42
43
44
RO
⎯
13
Event 3 state monitor
CH1
CH2
CH3
CH4
002D
002E
002F
0030
45
46
47
48
RO
⎯
14
Event 4 state monitor
CH1
CH2
CH3
CH4
0031
0032
0033
0034
49
50
51
52
RO
0: OFF
1: ON
⎯
15
Heater break alarm (HBA)
state monitor
CH1
CH2
CH3
CH4
0035
0036
0037
0038
53
54
55
56
RO
0: OFF
1: ON
⎯
16
Output state monitor
⎯
0039 57 RO
Bit
data
Bit 0: OUT1
Bit 1: OUT2
Bit 2: OUT3
Bit 3: OUT4
Bit 4 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 15]
When control output is specified, this function
is available only for a proportioning control.
⎯
17
Memory area soak time
monitor
CH1
CH2
CH3
CH4
003A
003B
003C
003D
58
59
60
61
RO
0 minutes 00 seconds to 199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to 99 hours 59 minutes:
0 to 5999 minutes
Data range of Area soak time can be selected
on the Soak time unit.
⎯
18
Integrated operating time
monitor
⎯
003E
62
RO
0 to 19999 hours
⎯
19
Holding peak value ambient
temperature monitor
CH1
CH2
CH3
CH4
003F
0040
0041
0042
63
64
65
66
RO
−
10.0 to
+
100.0
°
C (14.0 to 212.0
°
F)
⎯
20
Backup memory state
monitor
⎯
0043
67
RO
0: The content of the backup memory does
not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
Continued on the next page.