7. COMMUNICATION DATA MAP
IMR01Y35-E3
55
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
21 DO
energized/de-energized
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00AA
00AB
00AC
00AD
00AE
00AF
00B0
00B1
170
171
172
173
174
175
176
177
R/W
0: Energized
1: De-energized
0
22
DO output distribution
master channel module
address
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00B2
00B3
00B4
00B5
00B6
00B7
00B8
00B9
178
179
180
181
182
183
184
185
R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
−
1
23
DO output distribution
master channel selection
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00BA
00BB
00BC
00BD
00BE
00BF
00C0
00C1
186
187
188
189
190
191
192
193
R/W
1 to 99
1
24
DO manipulated output
value (MV) at STOP
mode
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00C2
00C3
00C4
00C5
00C6
00C7
00C8
00C9
194
195
196
197
198
199
200
201
R/W
−
5.0 to
+
105.0 %
−
5.0
25
DO output limiter (high)
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00CA
00CB
00CC
00CD
00CE
00CF
00D0
00D1
202
203
204
205
206
207
208
209
R/W
DO output limiter (low) to 105.0 %
105.0
26
DO output limiter (low)
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
00D2
00D3
00D4
00D5
00D6
00D7
00D8
00D9
210
211
212
213
214
215
216
217
R/W
−
5.0 % to DO output limiter (high)
−
5.0
27 Control
RUN/STOP
holding setting
⎯
00DA
218
R/W
0: Not holding (STOP start)
1: Holding (RUN/STOP hold)
1
28 Interval
time
⎯
00DB
219
R/W
0 to 250 ms
10