E1-17: Udc Ripple Alarm Select (When E1-18=0, ignore this setting)
E1-18: OverLoad Alarm for ? sec
Main Menu>Programming>ENT>Aux-Relay>ENT
z
If you want to switch on the Aux-Relay 1 when there is a battery voltage ripple alarm. This
setting (E1-17) can be used to choose between pre-alarm or normal alarm.
z
As with other Aux-Relay 2, setting a delay value (E1-18) must be specified also. This can be
done with Delay value for set Aux-Relay 1 ON when battery voltage ripple alarm (E1-18)
setting.
E2 Group (Setting Aux-Relay 1 OFF Condition)
E2-01: Load Lower than ? Amps
E2-02: Load Lower for ? sec
Main Menu>Programming>ENT>Aux-Relay>ENT
z
Use these settings to switch Aux-Relay 1 OFF. When the actual AC OUT Load is below a
certain value (E2-01) for a certain time (E2-02).
z
The corresponding Aux-Relay ON condition is
E1-01: Load Higher than ? Amps and
E1-02: Load Higher for ? sec.
※
Note: If setting E2-02 (E1-02)=0 sec (Initial setting), then the E2-01 (E1-01) is ignored.
E2-03: Udc Lower than ? Voltage
E2-04: Udc Lower for ? sec
Main Menu>Programming>ENT>Aux-Relay>ENT
z
Use these settings to switch off the Aux-Relay 1 when battery voltage becomes lower than a
certain limit (E2-03) for a certain time (E2-04)
※
Note: If E2-04=0 sec (Initial Setting), then E2-03 is ignored.
E2-05: Udc Higher than ? Voltage
E2-06: Udc Higher for ? sec
Main Menu>Programming>ENT>Aux-Relay>ENT
z
Use these settings to switch off the Aux-Relay 1 when battery voltage becomes higher than a
certain limit (E2-05) for a certain time (E2-06)
※
Note: If E2-06=0 sec (Initial setting), then E2-05 is ignored.
Summary of Contents for Invertek CombiPlus
Page 1: ......
Page 2: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 2...
Page 8: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 8 Layout...
Page 109: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 109 Chapter 8 Constants list...
Page 128: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 128 NOTES...