MODE 3:
Renewable Energy has Priority to Charge the batteries.
The Combi Inverter has Priority to Support the
AC load with AC Power Support.
When CombiPlus enters to MODE 3, B2-09(AC IN DynaCur Limit)=0 (Disable) and the value
of B2-20 (MODE3: ACINCurrent Lmt) will be loaded to B2-05.
INVERTER Mode:
z
When the battery voltage is not lower than (B2-14) voltage value, inverter mode takes
priority to supply voltage to AC OUT for load consumption.
(INVERTER ON+ ATS OFF + AC CHARGER OFF)
Battery
Shore Power
Ready
Load
ATS OFF
AC IN
AC OUT
3A
5A
B2-05=5A
3A
45A
Solar
Charger
Solar Panel
or