Rich electric Invertek CombiPlus User Manual Download Page 118

 

 

 
 
           

 

Rich Electric Co.    “CombiPlus” User Manual V7.19      Copyright 2009

                Page 118

 

 

 

 

Menu 

Group 

Function 

Constant 

LCD Display 

Range 

Unit 

Factory 

Remark 

Page

E8-01 

Aux2 Usage Select 

0~1 

0:Do not use Aux 

1: Use Aux 

98 

E8-02 

Aux2 Invert Select 

0~1 

0: Normal 

1: Invert switch 

98 

E8 Aux- 

Relay 2 

Option 

E8-03 

Aux2 notSwitchOff T 

0~1000 

1 min 

 

98 

E9-01 

Aux3 Usage Select 

0~1 

0:Do not use Aux 

1: Use Aux 

98 

E9-02 

Aux3 Invert Select 

0~1 

0: Normal 

1: Invert switch 

98 

E Aux-Relay 

E9 Aux- 

Relay 3 

Option 

E9-03 

Aux3 notSwitchOff T 

0~1000 

1 min 

 

98 

F1-01 

Solar Charger Enable 

0~1 

0: Disable 

1: Enable 

NOTE 5 

 

F1-02 Reset 

Amp-Hours 

0~1 

0: No 

1: Yes 

NOTE 5 

 

F Solar 

Charger  F1  Solar 

Charger 

F1-03 

Solar Monitor Sel 

0~10 

0: Sum of display 

1~10: independent 

display 

NOTE 5 

 

O1-01 

Power-ON Monitor Sel 

0~18 

NOTE 4 

43 

O1 Monitor 

Select 

O1-02 

Key Idle Detect Time 

10~600 

1sec 

180 sec 

 

43 

O2-01 

Key Pressed Beep Sel 

0~1 

0:Disable 

1:Enable 

44 

O2-02 Elapsed 

Time 

Reset 

0~60000  1hour 

0   

44 

O2-03 Elapsed 

Time 

Select 

0~1 

0:Power ON 

1: Run Time 

44 

O2-04 CombiPlus® 

Model 

 

 

 

 44 

O2-06 

MODE Key Hold Time 

2~10 

1sec 

5 sec 

 

44 

O2-07 

RUN/STOP KeyHoldTime 

2~10 

1sec 

2 sec 

 

45 

O2-08 

Auto Run Select 

0~1 

0: Manual 

1: Auto 

45 

Programm- 

ing 

O Operator 

O2 Key 

Selections 

O2-09 

Display IdleTime Set 

0~60 

1min 

10 min 

 

45 

Summary of Contents for Invertek CombiPlus

Page 1: ......

Page 2: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 2...

Page 3: ...tic Layout Multiple Ciruits AC Output 22 1 7 AC Cabling Schematic Layout Single Ciruit AC Output 23 1 8 Second Battery 24 1 9 Voltage Sense 24 1 10 Battery Temperature Sensor BTS 3 24 1 11 Three Sets...

Page 4: ...AC 3 Phase System 15 Modules 34 Chapter 3 Battery Types 3 1 Sealed Batteries 35 3 2 AGM 35 3 3 Gel 36 3 4 Flooded Batteries 36 3 5 Lead Calcium 37 3 6 Lead selenium 37 3 7 Lead Antimony 37 Chapter 4 O...

Page 5: ...E 4 Renewable Energy with AC Charger Backup Support 70 Chapter 6 Programming A Group Initialize 74 B Group General 77 C Group Inverter 86 D Group Battery Charger 88 E Group Aux Relay 92 O Group Operat...

Page 6: ...ng Vertical CombiPlus Appendix B LVD for Wall Mounting Vertical CombiPlus Appendix C C Tick for Wall Mounting Vertical CombiPlus Appendix D EMC for Table Mounting Horizontal CombiPlus Appendix E LVD f...

Page 7: ...dden loads on generator causing voltage spikes Interactive Power Sharing programmable AC input control system Four stage adaptive charging system with dual bank battery charging up to 140Amps 4 Amps s...

Page 8: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 8 Layout...

Page 9: ...ility when you are away from mains powered sites The CombiPlus has many unique features like its big brother the SuperCombi This includes stacking for increased power output 3 phase power option Requi...

Page 10: ...o low 9 9 e DC voltage ripple too high 9 9 f Temperature Sensor Transformer 105 105 Electronic Powerstage 70 70 Battery Temp BTS 3 50 50 Humidity 0 95 non condensing 0 95 non condensing Power support...

Page 11: ...Maximum Efficiency 82 84 85 84 86 89 Zero load Power W 8W Power Save 12W Normal 12W Power Save 18W Normal CHARGER Input Voltage Range VAC 180 265 VAC 94 138 VAC Input Frequency 45 55Hz 55 65 Hz Power...

Page 12: ...etection Time AC Input Fault 4 10 msec Trip Level AC Low Input to Inverter Default Setting 94 VAC 94 120V 110v Model 180 VAC 180 230V 230v Model Trip Level Inverter to AC Low Input Default Setting 101...

Page 13: ...Model Dimension for Wall Mounting Vertical CombiPlus 1500W CP 1500W 12 24 Unit mm AC IN CHARGER SOLAR CHARGER SOLAR PANEL INVERTER AC OUT ATS POWER Invertek CombiPlus DSPL ENT RUN STOP REMOTE R BATTER...

Page 14: ...biPlus User Manual V7 19 Copyright 2009 Page 14 Dimensions 1500watt Model Installation Holes for Wall Mounting Vertical CombiPlus 1500W CP 1500W 12 24 Backside Mounting Holes Bottom Mounting Holes 10...

Page 15: ...Dimension for Wall Mounting Vertical CombiPlus 3000W CP 3000W 12 24 Unit mm AC IN CHARGER SOLAR CHARGER SOLAR PANEL INVERTER AC OUT ATS POWER Invertek CombiPlus DSPL ENT RUN STOP REMOTE R BATTERY BUL...

Page 16: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 16 Dimensions 3000watt Model Installation Holes Backside Mounting Holes Bottom Mounting Hole 10 10 10 10 M 6 4 M8 4...

Page 17: ...CENSED ELECTRICIAN AND MUST CONFORM TO AS3000 WIRING REGULATIONS OR RELEVANT STANDARDS For other regions the installation and wiring should comply with relevant National Standards and Practices 1 1 Bo...

Page 18: ...and circuit breakers Try and keep the distance between the product and battery to a minimum in order to minimize cable voltage losses The system should always be earthed for lightning and to reduce t...

Page 19: ...AWG NOTE Consult your battery manufacturer for correct battery sizing for your application Battery cable sizes are based on recommended cable length of 2 meters Longer cable lengths will require large...

Page 20: ...labeled AC IN The terminal points are indicated clearly From left to right L phase N neutral and G earth External fuses or circuit breakers must be installed The AC input circuit breaker built in to t...

Page 21: ...IN AC Cable Size single Twin core and earth Model MAX Circuit Breaker Current Enclosed conduit Unenclosed free air 1500watt 25Amp 4mm 2 5mm 3000watt 50Amp 16mm 10mm 6000watt 100Amp 35mm 25mm THE OUTPU...

Page 22: ...g Schematic Layout Multiple Circuit AC Output ALL AC WIRING MUST BE CARRIED OUT BY A LICENSED ELECTRICIAN AND MUST CONFORM TO AS3000 WIRING REGULATIONS OR RELEVANT STANDARDS For other regions the inst...

Page 23: ...ng Schematic Layout Single Circuit AC Output ALL AC WIRING MUST BE CARRIED OUT BY A LICENSED ELECTRICIAN AND MUST CONFORM TO AS3000 WIRING REGULATIONS OR RELEVANT STANDARDS For other regions the insta...

Page 24: ...ers to connect to other appliances or to output the alarm signals 3 sets of relays can be programmed for respective function E Group Constants and can be practically applied which is one of the greate...

Page 25: ...cm For better ventilation please install the fan cover optional The Battery Temperature Sensor BTS voltage sensor V SENS and remote control panel RCP must be connected to Master The cables for each Co...

Page 26: ...unit is installed nearby wall side which Blocks the airflow coming to the unit The fan cover is needed The CombiPlus also supports connection of an External fan This is very useful when the CombiPlus...

Page 27: ...18 Multiple and 3 Phase Application When there is more than one CombiPlus in parallel connection or 3 phase connection the optional accessory fan covers are highly recommended to be installed for each...

Page 28: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 28 Chapter 2 Wiring Connections 2 1 Lower Front Panel Connection for Wall Mounting Vertical CombiPlus P G H I O M N L J K E F A B C D...

Page 29: ...r F Vsens Battery Voltage Sense Connecting terminal for Battery Voltage feedback G RY1 contact Connecting terminal for auxiliary contact 1 H RY2 contact Connecting terminal for auxiliary contact 2 I R...

Page 30: ...RY1 A C RY2 A C RY3 A C POS NEG B B AC INPUT BREAKER PORT A IN PORT B OUT PORT C EXT AC IN L N G AC OUT L N G WARNING Don t reverse the and of the battery This may cause internal damage AC IN CHARGER...

Page 31: ...A C RY2 A C RY3 A C POS NEG B B AC INPUT BREAKER PORT A IN PORT B OUT PORT C EXT AC IN L N G AC OUT L N G WARNING Don t reverse the and of the battery This may cause internal damage AC IN CHARGER SOLA...

Page 32: ...AC IN L N G AC OUT L N G WARNING Don t reverse the and of the battery This may cause internal damage AC IN CHARGER SOLAR CHARGER SOLAR PANEL INVERTER AC OUT ATS POWER Invertek CombiPlus DSPL ENT RUN S...

Page 33: ...AC IN L N G AC OUT L N G WARNING Don t reverse the and of the battery This may cause internal damage AC IN CHARGER SOLAR CHARGER SOLAR PANEL INVERTER AC OUT ATS POWER Invertek CombiPlus DSPL ENT RUN S...

Page 34: ...Plus DSPL ENT RUN STOP REMOTE R BATTERY BULK ABSOR FLOAT COM ERR 1 MODE 2 MODE 3 MODE 4 MODE ERR COM 1 0 Power Management Control System PORT A IN PORT B OUT PORT C EXT AC IN L N G AC OUT L N G AC IN...

Page 35: ...ommend constant voltage charging to 2 45 volts cell 14 7V For cycling applications charging to 14 4V or 14 5V is often recommended Typical float voltage of 13 5 13 8v AGM batteries are commonly replac...

Page 36: ...inverter systems over the years The advantages of flooded batteries are normally very cost effective Flooded batteries can offer good service life for deep cycle applications In cycling applications...

Page 37: ...cells are rugged and provide long service life with deep discharge capability However these batteries self discharge much faster and the self discharging increases up to five times the initial rate as...

Page 38: ...ctions of the Combi This switch in the ON position will by default resume functions previously running when the POWER switch was turned off The RUN STOP button changes the Combi between Standby and Op...

Page 39: ...Day or Night cloudy day 4 SOLAR CHARGER Solar module is charging the batteries No external solar charger is connected 5 AC OUT There is voltage at the AC OUT terminal 6 INVERTER Green Inverter is work...

Page 40: ...at Parameter Edit Before changing from one mode to another it has to stop running and be in STOP mode PB6 DSPL Multi display select key PB7 ENTER Data write in key PB8 UP Increment key PB9 DOWN Decrem...

Page 41: ...See Key Pressed Beep Select O2 01 menu Refer page 44 4 When the front panel is not in use it will go to sleep after a set period of time O1 02 Once any key is pressed the front panel display will ill...

Page 42: ...on modules status This is U Monitor Group constants Initialize Operation Condition Setting Group A Initialize Group Multi language setting constants initialization setting and constants modification a...

Page 43: ...monitor selections will be showed on LCD Display U1 05 Battery Voltage is the initial display shown z All the constants in U1 Group can be programmed U1 01 U 26 O1 02 Key Idle Detect Time Main Menu Pr...

Page 44: ...nstant O2 02 to reset elapsed time O2 03 Elapsed Time Select Main Menu Programming ENT Operator ENT Key Selections ENT Setting Function O2 03 0 Initial setting The elapsed time started to be counted a...

Page 45: ...ually or automatically Setting Function O2 08 0 Auto Run is active when pressing Run STOP key O2 08 1 Initial setting Auto Run is active when the power is on O2 09 LCD Display Idle Time Set Main Menu...

Page 46: ...enu Operation ENT Monitor ENT z Use constant U1 03 to monitor AC OUT voltage value in unit of 0 1V U1 04 AC OUT Current Main Menu Operation ENT Monitor ENT z Use constant U1 04 to monitor AC OUT curre...

Page 47: ...eration ENT Monitor ENT Use constant U1 10 to monitor the ON OFF status of 3 sets of Aux Relay RY1 RY2 RY3 Please see NOTE 2 in Chapter 5 of the User Manual U1 11 Elapsed Time Main Menu Operation ENT...

Page 48: ...unit of 1W U1 18 Solar Amp Hours Main Menu Operation ENT Monitor ENT z Use constant U1 18 to monitor solar Amp Hours value in unit of 1AH U1 19 Solar Total Amp Hours Main Menu Operation ENT Monitor EN...

Page 49: ...z Use constant U2 02 to monitor the last fault that has been recorded U2 03 AC IN Voltage Main Menu Operation ENT Fault Trace ENT z Use constant U2 03 to monitor the AC input voltage value in unit of...

Page 50: ...09 Battery Current Main Menu Operation ENT Fault Trace ENT z Use constant U2 09 to monitor the battery current value in unit of 0 1A when the current fault occurs U2 10 Control Mode Main Menu Operati...

Page 51: ...it of 0 1A when the current fault occurs U2 16 Solar Supply Power Main Menu Operation ENT Fault Trace ENT z Use constant U2 16 to monitor the solar supply power value in unit of 1W when the current fa...

Page 52: ...Use constant U3 02 to monitor the most recent second fault stored in the software U3 03 Fault Message 3 Main Menu Operation ENT Fault History ENT z Use constant U3 03 to monitor the most recent third...

Page 53: ...elapsed time before the most recent second fault occurs U3 07 Elapsed Time 3 Main Menu Operation ENT Fault History ENT z Use constant U3 07 to monitor the elapsed time before the most recent third fa...

Page 54: ...MODE 2 AC Generator has Priority to Support the AC Load with Dynamic Power Shifting MODE 3 Renewable Energy has Priority to Charge the batteries The Combi Inverter has Priority to Support the AC load...

Page 55: ...f CP 3000 242 When CombiPlus enters to MODE 1 B2 09 AC IN DynaCur Limit 0 Disable and the value of B2 18 MODE1 ACINCurrent Lmt will be loaded to B2 05 INVERTER Mode z When AC IN 0 A AC OUT load is com...

Page 56: ...ve Power Sharing Mode a z In this example All AC loads are off with the CombiPlus constant B2 05 5A AC IN Current Limit The AC CHARGER will not take more than 5A with limits to battery charge current...

Page 57: ...me small loads are switched on and load increase to 3A Only 5 3 2A is left to Charge the batteries and charge current is reduced to about 30A Note Shore current is automatically limited to 5A and the...

Page 58: ...r Sharing Mode c z The load is switched on and current consumption increase to 5A Nothing is left to charge the battery z The charge current is automatically reduced to 0A and the AC input circuit bre...

Page 59: ...here Power Assist is needed z The bidirectional converter starts operating as inverter to add 6A to the 5A that is available from the shore side Total 6 5 11A and no overload on the AC supply z As soo...

Page 60: ...c Power Shifting When CombiPlus enters to MODE 2 B2 09 AC IN DynaCur Limit 1 Enable and the value of B2 19 MODE 2 ACINCurrent Lmt will be loaded to B2 05 INVERTER Mode z When AC IN 0 A AC OUT load is...

Page 61: ...ve Power Sharing Mode a z In this example All AC loads are off with the CombiPlus constant B2 05 5A AC IN Current Limit The AC CHARGER will not take more than 5A with limits to battery charge current...

Page 62: ...me small loads are switched on and load increase to 3A Only 5 3 2A is left to Charge the batteries and charge current is reduced to about 30A Note Shore current is automatically limited to 5A and the...

Page 63: ...r Sharing Mode c z The load is switched on and current consumption increase to 5A Nothing is left to charge the battery z The charge current is automatically reduced to 0A and the AC input circuit bre...

Page 64: ...no mains available The Green Power Smart feature uses renewable energy such as solar wind and hydro generation to recharge the batteries and will only connect to the mains grid or start the generator...

Page 65: ...a backup generator to replenish this charge If the CombiPlus is installed in a boat or where there is no mains power available a signal can be sent to the generator to automatically start and stop it...

Page 66: ...s enters to MODE 3 B2 09 AC IN DynaCur Limit 0 Disable and the value of B2 20 MODE3 ACINCurrent Lmt will be loaded to B2 05 INVERTER Mode z When the battery voltage is not lower than B2 14 voltage val...

Page 67: ...lied by AC IN power z In Mode 3 The AC CHARGER will remain OFF The batteries will only be recharged by renewable energy input such as solar wind generator or DC generator charger z The difference betw...

Page 68: ...d adds and the current increases to 11A This is where Power Support function is needed ATS ON AC CHARGER OFF INVERTER ON Power Support Mode ON z As soon as the load reduces to less than 5A power assis...

Page 69: ...is recharged by other renewable energy source battery voltage is higher than B2 14 voltage value and longer than second time set in B2 15 inverter mode takes priority to supply voltage to AC OUT agai...

Page 70: ...en CombiPlus enters to MODE 4 B2 09 AC IN DynaCur Limit 0 Disable and the value of B2 19 MODE4 ACINCurrent Lmt will be loaded to B2 05 1 INVERTER Mode z When the battery voltage is not lower than B2 1...

Page 71: ...and longer than the second time set in B2 11 ATS will be switched on to ensure AC OUT to continuously the load At the moment AC OUT will be supplied by AC IN power At the same time the interactive po...

Page 72: ...ent increases to 11A This is where Power Support function is needed ATS ON AC CHARGER OFF INVERTER ON Power Support Mode ON z As soon as the load reduces to less than 5A any current that is left over...

Page 73: ...at z When the battery voltage is higher than B2 12 voltage value and longer than second time set in B2 15 inverter mode takes priority to supply voltage to AC OUT again for load consumption Battery Sh...

Page 74: ...tialize A1 Group Initialize A1 01 Access level z Use constant A1 01 to select the user constant access level This level determines which user constants can be changed and displayed Setting Function A1...

Page 75: ...Reserved under development A1 02 2 Reserved under development A1 02 3 Reserved under development A1 02 4 Reserved under development A1 02 5 Reserved under development A1 02 6 Reserved under developme...

Page 76: ...and press RUN STOP key and UP key at the same time till A1 05 parameter occurs 4 Enter the desired password max 4 digits 5 Press UP key to leave A1 05 Above procedure completes locking the constants s...

Page 77: ...o set the output frequency at INVERTER AC output Setting Function B1 01 0 Initial setting 50Hz at INVERTER AC output B1 01 1 60Hz at INVERTER AC output z B2 08 AC IN Frequency Range Setting Function W...

Page 78: ...B2 02 also changes Note B2 02 can be ignored for a short time when AC IN Waveform Check B2 06 is Disabled B2 06 0 z When the AC IN voltage drops due to the increasing charge current the AC CHARGER wi...

Page 79: ...ower Support enabled there is a minimum value for the AC input current limit Please see the note at Power Support page 71 B2 06 AC IN Waveform Check Main Menu Programming ENT General ENT Auto transfer...

Page 80: ...l z When ATS closes AC IN is transferred to AC OUT the Neutral is first disconnected from G terminal Setting Function B2 07 0 The internal ground relay is open with G terminal B2 07 1 Initial setting...

Page 81: ...atteries are fully charged Therefore no current from generator is drawn z At this moment we connect a load of 7A to the CombiPlus with this setting B2 09 disabled the CombiPlus would not react because...

Page 82: ...used to set ATS to be ON when the battery voltage is lower than B2 14 voltage value and longer than the second time set in B2 15 in MODE3 ATS ON INVERTER OFF AC CHARGER ON z MODE 3 B2 16 and B2 17 are...

Page 83: ...ine the actual AC current limit B2 20 MODE3 ACIN Current Lmt Main Menu Programming ENT General ENT Auto transfer Switch ENT z Use constant B2 20 to set the set the specific maximum AC input current in...

Page 84: ...he number of CombiPlus Master Slaves and set the limit accordingly So an example of setting the B2 05 10A in a parallel system with 3 CombiPlus would result in a limit of 3 10A 30A z Please Note If ho...

Page 85: ...nitial setting 2 3 Phase connection system is called Follower B4 02 1 2 3 Phase connection system is called Master B4 03 2 3 Phase Type Main Menu Programming ENT General ENT 2 3 Phase ENT z Use consta...

Page 86: ...3 C1 03 will automatically go to 11 6V 10 0 1 6 after C1 02 is changed to 10 0V C1 03 Battery Low V Restart Main Menu Programming ENT Inverter ENT z This setting forms a pair with Bat Low V Shut down...

Page 87: ...setting is a special setting for power Support mode when the CombiPlus is charging and due to a sudden load the AC IN current exceeds the AC IN Current Limit B2 05 the CombiPlus will switch to power S...

Page 88: ...only be changed by a qualified engineer z Do not use non rechargeable batteries z Batteries should be placed in a dry and well ventilated area during charging The product default settings are for cha...

Page 89: ...orption time from the Bulk time The maximum Absorption time of these charge curves is determined by Absorption Time D1 06 setting z The Adaptive Battery safe D1 02 3 curve has a special regulation in...

Page 90: ...rve is fixed D1 02 1 then this setting is used to determine the absorption time z In all other cases this setting determines the maximum absorption time D1 07 Float Voltage Main Menu Programming ENT C...

Page 91: ...urs z This setting can be disabled because it does not always indicate a problem when the bulk phase lasts very long The charge current can be very low due to limited AC input current and or AC loads...

Page 92: ...ngs to switch the Aux Relay 1 ON When battery voltage becomes lower than a certain limit E1 03 for a certain time E1 04 Note If E1 04 0 sec Initial setting then E1 03 is ignored E1 05 Udc Higher than...

Page 93: ...ttings a delay value E1 12 must be specified also This can be done with Delay value for set Aux Relay 1 ON when over temperature alarm E1 12 setting E1 13 Low Batt Alarm Select When E1 14 0 ignore thi...

Page 94: ...ese settings to switch Aux Relay 1 OFF When the actual AC OUT Load is below a certain value E2 01 for a certain time E2 02 z The corresponding Aux Relay ON condition is E1 01 Load Higher than Amps and...

Page 95: ...comes active when the charge bulk phase is finished for a certain time E2 09 z For the charge curve take a look at for instance the Charge Current D1 08 setting z This is useful when the Aux Relay 1 i...

Page 96: ...for sec Main Menu Programming ENT Aux Relay ENT z If you want to switch off the Aux Relay 1 when there is no low battery alarm this setting E2 14 can be used to choose between pre alarm or normal alar...

Page 97: ...mal alarm z As with other Aux Relay 1 setting a delay must be specified also This can be done with the Delay value for set Aux Relay 1 OFF when No Battery voltage Ripple Alarm E2 19 setting E3 Group S...

Page 98: ...his is used to invert the Aux Relay 1 So ON becomes OFF and OFF becomes ON In the program the labels are adapted to reflect this inversion E7 03 Aux1 not Switch Off Time Aux Relay 1 does not switch of...

Page 99: ...ain Menu Initialize Main Menu Group B Function B1 Output Frequency B1 01 0 Programming General Output Frequency 50Hz 50Hz MENU GROUP Function Parameters Parameter Edit Main Menu Group B Function B1 Ou...

Page 100: ...tery RippleVoltag CPU ID 1 AC IN Voltage U1 06 0 0V U1 13 CPD0706 U1 01 220V Battery Current CPU ID 2 U1 07 0A U1 14 CPM0701 Function U2 Fault Trace Function U3 Fault History Function U1 Monitor MENU...

Page 101: ...y B1 01 0 Programming General Output Frequency 50Hz 50Hz Entry Accepted Group C Function B2 B1 01 1 Inverter Auto Transfer Switch 60Hz Group D Function B3 Charger Parallel System Group E Function B4 A...

Page 102: ...ct Solar Charger Output Frequency B2 04 270V Group O AC IN Current Limit AC IN Low Disconnect Operator B2 05 16A 1 81V Group B AC IN Waveform Check General Active AC IN Low Disconnect 18 1 V Ground Re...

Page 103: ...up B General Main Menu Programing Function B3 B3 01 DSPL DSPL ENTER DSPL ENTER DSPL ENTER DSPL ENTER DSPL ENTER MENU GROUP Function Parameters Parameter Edit Main Menu Operation Main Menu Initialize M...

Page 104: ...tage Inverter Out Voltage Inverter C1 01 230V 23 0 V Entry Accepted Group D DC In Low Shut down Inverter Out Voltage Charger C1 02 18 00V 23 1 V Group E DC In Low Restart Aux Relay C1 03 21 80V Group...

Page 105: ...ction D1 D1 01 DSPL DSPL ENTER DSPL ENTER DSPL ENTER DSPL ENTER MENU GROUP Function Parameters Parameter Edit Main Menu Operation Main Menu Initialize Main Menu Group B Programming General Group C Inv...

Page 106: ...for sec Load Higher than A Solar Charger Set Aux Relay1 OFF E2 02 0sec 3 3 3 A Group O Function E3 Udc Lower than V Not Charge for Sec Operator Set Aux Relay2 ON E2 03 23 50V E2 07 0sec Group B Functi...

Page 107: ...1 F1 01 DSPL DSPL ENTER DSPL ENTER DSPL ENTER DSPL ENTER MENU GROUP Function Parameters Parameter Edit Main Menu Operation Main Menu Initialize Main Menu Group B Function O1 Power On Monitor Sel O1 01...

Page 108: ...ctions Enable Enable Entry Accepted Group D Elapsed Time Set O2 01 0 Charger O2 02 0Hr Disable Group E Elapsed Time Select Aux Relay Power ON Group F CombiPlus Model Auto Run Select Solar Charger O2 0...

Page 109: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 109 Chapter 8 Constants list...

Page 110: ...r Charger Status NOTE 5 48 U1 16 Solar Supply Current 0 1A NOTE 5 48 U1 17 Solar Supply Power 1W NOTE 5 48 U1 18 Solar Amp Hours 0 1AH NOTE 5 48 U1 19 Solar Total Amp Hours 0 1AH NOTE 5 48 U1 Monitor...

Page 111: ...Constant Set 74 A1 02 Select Language 0 0 English 75 A1 03 Init Parameters 0 1 1 0 0 No Initialize 1 Default Setting 75 Initialize A Initialize A1 Initialize A1 04 Password 1 0 999 1 0 76 B1 Output F...

Page 112: ...MODE 3 BatHi S ATSOFF 0 255 1 sec 60 sec 82 B2 18 MODE1 ACINCurrent Lmt NOTE 3 0 1A NOTE 3 83 B2 19 MODE2 ACINCurrent Lmt NOTE 3 0 1A NOTE 3 83 B2 20 MODE3 ACINCurrent Lmt NOTE 3 0 1A NOTE 3 83 B2 21...

Page 113: ...NOTE 3 0 01V NOTE 3 90 D1 08 Charge Current NOTE 3 1A NOTE 3 90 D1 09 Stop After 10Hr Bulk 0 1 1 1 0 Disable 1 Enable 91 D Charger D1 Charger D1 10 Equalize Mode Select 0 1 1 1 0 Disable 1 Enable 91...

Page 114: ...3 94 E2 04 Udc Lower for sec 0 255 1sec 0sec 94 E2 05 Udc Higher than V NOTE 3 0 01V NOTE 3 94 E2 06 Udc Higher for sec 0 255 1sec 0sec 94 E2 07 Charging for sec 0 255 1sec 0sec 95 E2 08 Fan Off for s...

Page 115: ...97 E3 12 Temp Alarm for sec 0 255 1sec 0sec 6 19 E3 13 Low Batt Alarm Sel 0 1 1 0 0 Alarm 1 Pre alarm 97 E3 14 Low Batt for sec 0 255 1sec 0sec 97 E3 15 Overload Alarm Sel 0 1 1 0 0 Alarm 1 Pre alarm...

Page 116: ...97 E5 01 Load Higher than A NOTE 3 0 01A NOTE 3 97 E5 02 Load Higher for sec 0 255 1sec 0sec 97 E5 03 Udc Lower than V NOTE 3 0 01V NOTE 3 97 E5 04 Udc Lower for sec 0 255 1sec 0sec 97 E5 05 Udc Highe...

Page 117: ...sec 0 255 1sec 0sec 97 E6 09 Charge Finished Min 0 1000 1min 0 97 E6 10 RY3 not ON for mins 0 1000 1min 0 97 E6 11 AC IN Loss for sec 0 255 1sec 0sec 97 E6 12 No Temp Alarm Sel 0 1 1 0 0 Alarm 1 Pre...

Page 118: ...r Charger Enable 0 1 1 1 0 Disable 1 Enable NOTE 5 F1 02 Reset Amp Hours 0 1 1 0 0 No 1 Yes NOTE 5 F Solar Charger F1 Solar Charger F1 03 Solar Monitor Sel 0 10 1 0 0 Sum of display 1 10 independent d...

Page 119: ...Fault Udc ripple 0 OK 1 Udc ripple Pre alarm OL 0 OK 1 Over load pre alarm Battery Low 0 OK 1 Battery low pre alarm Remoter 0 Remoter disconnect 1 Remoter connect AC OUT 0 No output 1 output AC IN 0...

Page 120: ...1 1V 187V 229 269 1V 265V 230 270 1V 270V CP 1500 242 180 230 1V 180V 181 231 1V 187V 229 269 1V 265V 230 270 1V 270V CP 3000 242 180 230 1V 180V 181 231 1V 187V 229 269 1V 265V 230 270 1V 270V CP 150...

Page 121: ...6 0 01A 13 30A CP 1500 242 24 0 32 0 0 01V 28 80V 24 0 32 0 0 01V 27 60V 0 35 1A 17A 0 29 3 0 01A 6 65A CP 3000 242 24 0 32 0 0 01V 28 80V 24 0 32 0 0 01V 27 60V 0 70 1A 35A 0 58 6 0 01A 13 30A CP 150...

Page 122: ...CP 3000 121 0 17 5 0 01V 16 0V CP 1500 241 0 35 0 0 01V 32 0V CP 3000 241 0 35 0 0 01V 32 0V NOTE 4 Parameter Setting LCD Display 0 AC IN Voltage 1 AC IN Current 2 AC OUT Voltage 3 AC OUT Current 4 Ba...

Page 123: ...lues 7 Change A1 01 0 Operation only factory setting is A1 01 1 Constants set 8 Go to A1 04 and press RUN STOP key and UP key at the same time till A1 05 parameter occurs 9 Enter the desired password...

Page 124: ...value range blink The battery voltage is low Charge the battery or check the battery connections The CombiPlus cuts out because the battery voltage is too low Charge the battery or check the battery...

Page 125: ...cables and reset the CombiPlus Power OFF and ON again blink Battery charger is not in normal charging status to cause battery voltage too high Incorrect battery voltage connection 12V system but conne...

Page 126: ...er is not functioning CombiPlus internal circuit breaker has tripped Reset the internal circuit breaker Incorrect charging current Set the charging current at between 0 1 0 2 battery capacity A defect...

Page 127: ...capacity A defective battery Replace the battery The battery is overcharged The battery is too hot Connect a Battery Temperature Sensor BTS 3 Battery over temperature 50 1 Allow battery to cool Down...

Page 128: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 128 NOTES...