Rich Electric Co. “CombiPlus” User Manual V7.19 Copyright 2009
Page 67
Mode 3
Interactive Power Sharing Mode
z
When AC IN power is ready, INVERTER is active and battery voltage is lower than B2-14
voltage value and longer than the second time set in B2-15, ATS will be switched on to
ensure AC OUT to continuously supply the load. At the moment, AC OUT will be supplied
by AC IN power.
z
In Mode 3 The AC CHARGER will remain OFF. The batteries will only be recharged by
renewable energy input such as solar, wind generator or DC generator charger.
z
The difference between MODE 3 and MODE 4 is that in MODE 3, when AC IN power is
ready, AC CHARGER is off and the battery is charged only by other renewable energy
sources. This is why MODE 3 is called Green Power as Priority Support Mode
(INVERTER OFF+ ATS ON + AC CHARGER OFF)
Battery
Shore Power
Load
ATS ON
AC IN
AC OUT
5A
B2-05=5A
3A
Solar
Charger
Solar Panel
or
3A
AC Charger
OFF