![Rich electric Invertek CombiPlus User Manual Download Page 43](http://html1.mh-extra.com/html/rich-electric/invertek-combiplus/invertek-combiplus_user-manual_1454301043.webp)
Rich Electric Co. “CombiPlus” User Manual V7.19 Copyright 2009
Page 43
4.4 Main Menu : Programming “Operator”
Main Menu: Programming
“Operator”
Monitor Select…….
O1-01: Power ON LCD Monitor Select
Main Menu>Programming>ENT>Operator>ENT>Monitor Select>ENT>
z
After power of the CombiPlus® is on, the monitor selections will be showed on LCD
Display, U1-05 Battery Voltage is the initial display shown.
z
All the constants in U1 Group can be programmed (U1-01~U-26).
O1-02: Key Idle Detect Time
Main Menu>Programming>ENT>Operator>ENT> Monitor Select >ENT>
z
Use constant O1-02 to set the idle time when the keyboard is not operated and once
any key is pressed, the display will return to the LCD monitor selection value set in
constant O1-01.
z
Initial Setting=180 sec, setting range: 10~600 sec.