The absorption voltage has
been set to an incorrect
value.
Adjust the absorption
voltage to the correct value.
The battery is overcharged.
The float voltage has been
set to an incorrect value.
Adjust the float voltage to
the correct value.
The battery is too small.
Reduce the charging current
or use a battery with a higher
capacity.
A defective battery.
Replace the battery.
The battery is overcharged.
The battery is too hot.
Connect a Battery
Temperature Sensor (BTS-3)
Battery over temperature
(
>
50
℃
)
1. Allow battery to cool
Down.
2. Place battery in a cool
Environment.
3. Check for shorted cells.
Battery charge current drop
to 0 A when the absorption
voltage is reached.
Battery Temperature Sensor
(BTS-3) is faulty
1.
Unplug Battery
Temperature Sensor
(BTS-3) from
“CombiPlus®”
and power
off the “CombiPlus®”
then wait 5 seconds and
Power on again.
2.
If the “CombiPlus®” AC
CHARGE normally, the
BTS-3 is faulty and
needs to be replaced.
Summary of Contents for Invertek CombiPlus
Page 1: ......
Page 2: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 2...
Page 8: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 8 Layout...
Page 109: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 109 Chapter 8 Constants list...
Page 128: ...Rich Electric Co CombiPlus User Manual V7 19 Copyright 2009 Page 128 NOTES...