Wiring in Control Cabinet
Special caution must be exercised when the unit is wired:
1. Route the unit power supply cable separately from other equipment power supply
cables.
2. Run the power supply cable and signal cables separately. Do not bundle them together.
3. Run coaxial cables connected to Network Cards and/or T-Boxes and other cables
separately. Do not bundle them together.
4. Use twisted pair of wires of 0.75 mm
2
through 2.0 mm
2
as the power supply cable to
prevent the power voltage from dropping below the minimum requirement.
5. For connection of the cable to the terminal block, use close-loop-type pressure terminal.