3. The operational ambient temperature should be 0
~
55 degrees C. To prevent the
temperature from rising above the range, provide sufficient space to allow appropriate
airflow for ventilation and enough capacity for cooling fans in the cabinet.
The maximum power dissipation of PSC7000 series is 75W per controller unit.
4. PSC7000 must be placed at least 200 mm away from power cable as shown in Fig. 4-5.
Fig. 4-5 Space Requirement for Wiring of Power Cable
Control Cabinet
Power Cable
2
0
0
m
m
o
r
m
o
re
200 mm
or more
Example of PSC7000 System