Chapter 19 BACnet signals
Analogue inputs
Object name
Object-ID
Description
Unit
Writable
RC_Actual_R.RegioRoomTemp
Analog input, 0 Room temperature
°C
No
RC_Actual_R.RegioAIChangeOver
Analog input, 1 Change over temperature
°C
No
RC_Actual_R.RegioAnaIn1
Analog input, 2 Value of analogue input 1
°C
No
RC_Actual_R.RegioUAnaIn1
Analog input, 3 Value of universal analogue input 1
V
No
RC_Actual_R.RegioRoomCO2
Analog input, 4 CO
2
input value
ppm
No
RC_Actual_R.RegioSupplyAirTemp
Analog input, 5 Supply air temperature
°C
No
RC_Actual_R.RoomFlow
Analog input, 6 Air flow
l/s
No
RC_Actual_R.VoltInput
Analog input, 7 Value on analogue input 2
V
No
Analogue values
Object name
Object-ID
Description
Unit Writable
RC_Actual_R.RegioUAnaOut1
Analog value, 0
Value of universal analogue
output 1
V
No
RC_Actual_R.RegioUAnaOut2
Analog value, 1
Value of universal analogue
output 2
V
No
RC_Actual_R.RegioSetPAdjustment
Analog value, 2
Setpoint adjustment from
internal device
°C
No
RC_Actual_R.RegioPIDSetP
Analog value, 3
Controller setpoint
°C
No
RC_Actual_R.RegioPIDOutput
Analog value, 4
Controller output
%
No
RC_Actual_R.RegioHeatOutput
Analog value, 5
Heat output
%
No
RC_Actual_R.RegioCoolOutput
Analog value, 6
Cool output
%
No
RC_Setp_R.RegioOccSetPHeat
Analog value, 7
Room base setpoint heating
°C
Yes
RC_Setp_R.RegioOccSetPCool
Analog value, 8
Room base setpoint cooling
°C
Yes
RC_Setp_R.RegioUnOccSetPHeat
Analog value, 9
Room heat setpoint in
unoccupied mode
°C
Yes
RC_Setp_R.RegioUnOccSetPCool
Analog value, 10
Room cool setpoint in
unoccupied mode
°C
Yes
RC_Setp_R.RegioFrostSetP
Analog value, 11
Frost protection setpoint
°C
Yes