88
Chapter 19
BACnet signals
Regio Midi manual
Object name
Object-ID
Description
Values
Writable
RC_Setp_X.RegioFanSelect
Multistate
value, 2
Fan mode select
1=Off
2=Manual speed 1
3=Manual speed 2
4=Manual speed 3
5=Auto
6=Auto 2
7=Auto 1
Yes
RC_Setp_X.RegioForcedVentSelect Multistate
value, 3
Manual/Auto forced
ventilation
1=Off
2=Manual On
3=Auto
Yes
RC_Setp_X.RegioChangeOverSelect Multistate
value, 4
Manual/Auto change-over 1=Heating
2=Cooling
3=Auto
Yes
RC_Setp_X.RegioRemoteState
Multistate
value, 5
Remote control unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
6=No remote control
Yes
RC_Non_Modbus.RegioButtonActiv
eConf
Multistate
value, 6
Active buttons
1=No buttons
2=Occupancy button
only
3=INCREASE/DECR
EASE only
4=Occupancy button
and
INCREASE/DECREA
SE
5=Fan button only
6=Occupancy button
and fan button
7=INCREASE/DECR
EASE and fan button
8=All buttons
Yes
Device
The device object contains two writable properties; Description and Location. Description can
be 17 characters long, and Location can be 33 characters long, if using single byte character
encoding.