Regio Midi manual
Chapter 19
BACnet signals
85
Object name
Object-ID
Description
Unit Writable
RC_Setp_R.RegioSetPOffset
Analog value, 12
Setpoint adjustment
°C
Yes
RC_Setp_R.RegioHeatOutputManual
Analog value, 13
Manual value heating output
%
Yes
RC_Setp_R.RegioCoolOutputManual
Analog value, 14
Manual value cooling output
%
Yes
RC_Setp_R.RegioRoomTempRemote
Analog value, 15
Remote control of room
temperature
°C
Yes
RC_Setp_R.RegioStandbySetPDeadBand
Analog value, 16
Deadband in Standby mode
°C
Yes
RC_Setp_R.RegioCVDeadband
Analog value, 17
Deadband control valve
%
Yes
RC_Setp_R.RegioAIChangeOverDiffHeat
Analog value, 18
Difference between media
temperature and room
temperature to switch to
heating control
K
Yes
RC_Setp_R.RegioAIChangeOverDiffCool
Analog value, 19
Difference between media
temperature and room
temperature to switch to
cooling control
K
Yes
RC_Setp_R.RegioRoomTempHighLimit
Analog value, 20
Alarm limit for high room
temperature
°C
Yes
RC_Setp_R.RegioRoomTempLowLimit
Analog value, 21
Alarm limit for low room
temperature
°C
Yes
RC_Setp_R.RegioFlow_0V
Analog value, 22
Flow at 0 V input signal at AI2 l/s
Yes
RC_Setp_R.RegioFlow_10V
Analog value, 23
Flow at 0 V input signal at AI2 l/s
Yes
RC_Setp_R.RegioThermostatHystHeat
Analog value, 24
Hysteresis when On/Off
control and Heat control
K
Yes
RC_Setp_R.RegioThermostatHystCool
Analog value, 25
Hysteresis when On/Off
control and Cool control
K
Yes
RC_Setp_R.RegioMinHeat
Analog value, 26
Minimum heat output at Heat
control
%
Yes
RC_Setp_R.RegioMinECFanSpeed
Analog value, 27
Minimum speed for the EC fan %
Yes
RC_Setp_R.RegioMaxECFanSpeed
Analog value, 28
Maximum speed for the EC fan %
Yes
RC_Setp_R.RegioAnaOut3
Analog value, 29
Value on universal analogue
output 3
V
No
RC_Setp_R.RegioUO3Output
Analog value, 30
UO3 Output (0…100 %)
%
No
RC_Actual_R.RegioPID2Setp
Analog value, 31
Calculated supply air setpoint
°C
No
No function
Analog value, 32-34
RC_SetpExt_R.RegioCO2LimitLow
Analog value, 35
CO
2
value when damper starts
to open
ppm Yes
RC_SetpExt_R.RegioCO2LimitHigh
Analog value, 36
CO
2
value when damper is
fully open
ppm Yes