60
Chapter 14
Display handling
Regio Midi manual
Configuration menu blocking
This function prevents unauthorised access to the configuration menu using the buttons on the
front of the device. When the function is active, all buttons will function normally except for
the configuration menu no longer being accessible when INCREASE and DECREASE are
pressed simultaneously. The function can be activated via the display, Regio tool
©
and
Modbus. Please note that if the function is activated via the display, re-entering the parameter
list via the display will be prevented. The function must then be deactivated using Regio tool
©
.
Parameter list
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter
number
Description
FS
1
Basic heating setpoint
22°C
2
Basic cooling setpoint
24°C
3
Neutral zone at standby,
Heating setpoint = Basic sp. heating-3 by default
Cooling setpoint = Basic sp.3 by default
3°C
4
Heating setpoint at Unoccupied
15°C
5
Cooling setpoint at Unoccupied
30°C
6
Frost protection setpoint
8°C
7
P-band for room controller
10°C
8
I-time for room controller
300 s
9
The difference between the temperature in the room and the media
temperature for change-over to cooling
3K
10
The difference between the temperature in the room and the media
temperature for change-over to heating
4K
11
Control mode:
0=Heating
1= Heating / Heating
2= Heating or Cooling via change-over
3= Heating / Cooling
4= Heating / Cooling with VAV-control and forced ventilation
5= Heating / Cooling with VAV-control
6= Cooling
7= Cooling / Cooling
8= Heating / Cooling/VAV (C3-models, except RC-C3DFOC)
9=Heating / Heating or Cooling via change-over (only available on models
with fan control)
10 = Change-over with VAV function
3
12
Time in Bypass mode
120 min
13
Disconnect timer with Occupancy/Unoccupancy
10 min
14
Switch-on delay for Occupancy
0 min
15
State connected sensor on AI1:
0=Internal sensor
1=External room sensor
2=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
3-10 = No function
11 = Supply air temperature limitation sensor
0
16
State connected sensor on UI1: (All models except RC-C3DOC,
RCC-C3DOCS, RC-C3DFOC )
0=None
1=Change-over digital
2=Change-over analogue
2
17
State connected sensor on DI1:
0=Not active
1=Window contact
2= No function
3= Presence detector
4=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC )
5-6=No function
1