Parameter menu
It is possible to set different parameter values in a parameter menu. The parameter menu is
accessed by simultaneously holding the INCREASE and DECREASE buttons pressed for
about 5 seconds and then pressing the INCREASE button twice. The Service indication will
be displayed.
The display will initially show the parameter number “1”. Use the INCREASE and
DECREASE buttons to scroll between parameters.
Press the Occupancy button to select the desired parameter. The parameter number will be
replaced by the parameter value. The value can be changed using the INCREASE and
DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly
and then with increasing speed in 3 – 4 steps with 2 – 3 seconds between steps.
Acknowledge/Regret
To acknowledge and store a set parameter value, press the Occupancy button again, the display
then returns to showing the parameter number. To retrieve the original value, i.e. the value
before change, press the INCREASE and DECREASE buttons at the same time. The original
value is shown on the display.
Return
After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are
pressed at the same time while in the menu, the display returns to the normal view. Exit is
shown on the display after the last parameter. The parameter menu is exited by pressing the
Occupancy button while in Exit. Pressing on INCREASE goes to the first parameter and
pressing on DECREASE goes to the last parameter.
Blocking of buttons
To prevent unauthorised users from accessing important functions, Regio controllers have a
built-in function for blocking button access. As seen in the below tables, blocking may take
place in different ways. The INCREASE/DECREASE buttons are always blocked/unblocked
simultaneously. If the INCREASE/DECREASE buttons are blocked, the parameter menu can
still be reached normally. Parameter 108 is used for configuration.
For models without a fan button and configuration options 4-6, the function remains the same
as for options 0-3.
Configuration options
Button function
0
No button is active
1
Only Occupancy button active
2
Only INCREASE/DECREASE buttons active
3
Occupancy and INCREASE/DECREASE buttons active
4
Only fan button active
5
Occupancy and fan buttons active
6
INCREASE/DECREASE and fan buttons active
7
All buttons active
Configuration
options
Occupancy
button active
INCREASE/DECREASE
buttons active
Fan button
active
0
1
X
2
X
3
X
X
4
X
5
X
X
6
X
X
7
X
X