64
Chapter 14
Display handling
Regio Midi manual
Parameter
number
Description
FS
91
Function to prevent user from setting manual fan speed if fan should not run
due to cooling/heating output according to parameter 50.
0 = Not active
1 = Active
0
92
Fan boost function. Activation time:
0 = Not active
1-10 = The function is active for 10 s.
10-600 = Total activation time
0
93
Boost function, configuration:
0 = Heating mode only
1 = Cooling mode only
2 = Both heating and cooling mode
1
94
Fan kickstart. The fan will run 100 % when starting up for the set time.
0 = Not active
1-10 = Active for set time (seconds)
0 seconds
97
Activate presence if CO
2
level is higher (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
800ppm
98
Deactivate presence if the CO
2
level is lower than the limit minus this
hysteresis (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
160ppm
100
Filter factor for CO
2
-input (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
0.2
101
Offset for internal CO
2
sensor reading
0ppm
104
CO
2
-level at 0 V (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
0ppm
105
CO
2
-level at 10 V (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
2000ppm
108
Button function configuration:
0 = No button is active
1 = Only Occupancy button active
2 = Only INCREASE/DECREASE buttons active
3 = Occupancy and INCREASE/DECREASE buttons active
4 = Only fan button active
5 = Occupancy and fan buttons active
6 = INCREASE/DECREASE and fan buttons active
7 = All buttons active
7
109
Activate parameter menu access via display:
0 = Not active
1 = Active
NOTE:
Activating this function via the display will prevent re-entry! If so,
parameter menu access may be activated again using Regio tool
©
.
0
110
Activate manual bypass timer setting. When the function is active, the user
may step through bypass time in 1 hour increments.
0 = Not active
1 = Active
0
112
Min limit for VAV-damper at CO
2
-control (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
600ppm
113
Max limit for VAV-damper at CO
2
-control (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
800ppm
114
This parameter defines the protocol to be used:
0=EXOline/Modbus
1=BACnet MS/TP
0
115
BACnet MS/TP MAC address:
0-127=master address
128-254=slave address
Factory set (00-
99)
116
Low 4 figures of the BACnet device ID. 0-9999
Factory set
117
High 3 figures of the device ID.
Factory set
118
BACnet MS/TP Max master.
127
119
COMbus speed:
0=9600
1=19200
2=38400
3=76800 (only BACnet)
0
120
COMbus reset.
When activated (1) it resets the communication to default settings
0 (deactivated)
121
Min limit for EC fan (%)
10 %