Regio Midi manual
Chapter 19
BACnet signals
87
Object name
Object-ID
Description
Values
Writable
RC_Setp_L.RegioComDefaults
Binary
value, 11
Resets communication settings
to default values
ACTIVE/
INACTIVE
Yes
RC_Setp_L.RegioBlockConfig
Binary
value, 12
Prevents unauthorised access to
the configuration menu via
controller buttons
ACTIVE/
INACTIVE
Yes
All binary values have normal polarity.
Loop
Object name
Object-ID
Description
Regulator
Loop, 0
The Regio Regulator
Multistate inputs
Object name
Object-ID
Description
Values
Writable
RC_Actual_X.RegioFanSwitch
Multistate
input, 0
Fan switch state
1=OFF
2=LOW
3=MEDIUM
4=HIGH
5=AUTO
No
RC_Actual_X.RegioUnitState
Multistate
input, 1
Current unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=Bypass
No
RC_Actual_X.RegioControllerState
Multistate
input, 2
Current controller state
1=Off
2=Heating
3=Cooling
No
RC_Actual_X.RegioFanSpeed
Multistate
input, 3
Current fan speed
1=Off
2=Fan speed 1
3=Fan speed 2
4=Fan speed 3
No
Multistate values
Object name
Object-ID
Description
Values
Writable
RC_Setp_X.RegioHeatOutputSelect Multistate
value, 0
Manual/Auto heat output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.RegioCoolOutputSelect Multistate
value, 1
Manual/Auto cool output
1=Off
2=Manual output
3=Automatic output
Yes