62
Chapter 14
Display handling
Regio Midi manual
Parameter
number
Description
FS
42
Select if setpoint or actual value is to be shown in the display.
0=Actual value
1=Heat setpoint
2=Cool setpoint
3=Average value of heating and cooling setpoint
4=Only setpoint offset
5= CO
2
concentration in the room in ppm (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
6=Heating sesetpoint offset
7=cooling ssetpoint offset
8=Average of heating and cooling ssetpoint offset
9=The calculated flow in the duct in l/s (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
0
43
Highest permitted setpoint adjustment upwards
3°C
44
Highest permitted setpoint adjustment downwards
3°C
45
Pre-set operating mode:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied. Forced ventilation is not set in Occupied mode.
3
46
State operating mode by pressing the occupancy button for 5 s:
0=Off
1=Unoccupied.
1
47
Select operating mode for central control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No central control
5
48
Min flow at cool output when control mode Heating/Cooling with VAV-
control is selected
Min flow at Y3 output when control mode Heating/Cooling/VAV is selected
20 %
49
Max flow on Y3 output when control mode Heating/Cooling/VAV is selected
and in heating mode
0 %
50
Configuration of fan control:
0=No control
1=Fan is controlled by heating demand
2=Fan is controlled by cooling demand
3=Fan is controlled by both heating and cooling demand
3
51
Start signal in % for fan speed 1 on heating or cooling control
5%
52
Start signal in % for fan speed 2
60%
53
Start signal in % for fan spped 3
100%
54
Hysteresis for start/stop of fans
5%
55
State number of speeds for the fan (1, 2 or 3)
3
56
Temperature compensation on AI1
0°C
57
Temperature compensation on UI1
0°C
58
Temperature compensation on internal room sensor
0°C
59
Filter factor for analogue temperature inputs
0,2
60
State NO/NC digital input 1:
0=NO (Normally open)
1=NC (Normally closed)
0
61
State NO/NC digital input 2:
0=NO (Normally open)
1=NC (Normally closed)
1
62
State NO/NC universal input 1:
0=NO (Normally open)
1=NC (Normally closed)
0
63
Manual/Auto Heating output:
0=Off
1=Manual
2=Auto
2
64
Manual/Auto cooling output:
0=Off
1=Manual
2=Auto
2