Regio Midi manual
Chapter 14
Display handling
65
Parameter
number
Description
FS
122
EC fan max limitation (V)
10
123
VAV-damper max limitation (%), control modes 5, 6 and 9
100 %
122
Max limit for EC fan (%)
100 %
125
Model
Factory set
(read only)
126
Version Major
Factory set
(read only)
127
Version Minor
Factory set
(read only)
128
Version Branch
Factory set
(read only)
129
Revision
Factory set
(read only)
132
Basic flow, Standby
10 %
133
Basic flow when no presence (Unoccupied)
10 %
134
Basic flow, Off
0 %
144
Period time for VAV-actuators with thermal actuators
60 s.
145
Select VAV-actuator function (NO/NC)
0 = NC (normally closed)
1 = NO (normally open)
0
146
Supply air max limitation for cascade control and heating control
35°C
147
Supply air min limitation for cascade control and heating control
24°C
148
Supply air max limitation for cascade control and cooling control
24°C
149
Supply air min limitation for cascade control and cooling control
12°C
150
Cascade factor between room controller and supply air controller
3°C
151
Frost protection temperature for supply air when supply air temperature
limitation is active
8°C
152
Activate supply air temperature limitation for:
0 = Heating control
1 = Cooling control
2 = Both heating and cooling control
1
153
Select simple or advanced analog change-over function
0 = Simple
1 = Advanced
1
154
Use valve exercise
0 = Never
1 = Regularly
2 = Regularly and at power-up
3 = Regularly, at power-up and when changing state to Occupied
1
Table 15. Parameter list