Regio Midi manual
Chapter 14
Display handling
61
Parameter
number
Description
FS
18
State connected sensor on DI2:
1=Window contact
2=Condensation sensor
3=No function
4=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC )
5 = No function
6 = No function
7 = Run indication
2
20
State connected function on UO1:
0=None
1=Thermal actuator heat
2= None
3=Heating actuator 0...10 V
4= None
5=On/off actuator heat
6= None
3
21
State connected function on UO2:
0= None
1= None
2=Thermal actuator cool
3= None
4=Cooling actuator 0…10 V
5= None
6=On/off actuator cool
4
22
State connected function on UO3:
0= None
1=Forced vent. digital
2=Analogue output (OEM)
3 = Lighting control
4 = Analogue output
5=Control of EC fan (RC-C3-models)
1
24
Y3 output in manual mode (only if Y3 is configured as an analogue output;
not available for RC-C3DFOC)
0 %
28
State output signal range for Y3-actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
29
State output signal range for heating actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
30
State output signal range for cooling actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
31
Period time for heating actuators with thermal actuator
60 s
32
Period time for cooling actuators with thermal actuator
60 s
33
Run time for heating actuators with increase/decrease actuators
120 s
34
Run time for cooling actuators with increase/decrease actuators
120 s
35
Neutral zone for increase/decrease actuators
2%
36
Time in hours between exercise of heating actuators
23h
37
Time in hours between exercise of cooling actuators
23h
38
Hysteresis for on/off actuators and heating
2K
39
Hysteresis for on/off actuators and cooling
2K
40
Minimum limit for the heat output
20 %
41
The fan will never stop
0=OFF
1=ON
0