Chapter 7
Control modes
41
Features for RC-C3DOC, RCC-C3DOCS, C3DFOC
0…10 V input
The 0…10 V input used as a CO
2
input for RC-C3DOC, RCC-C3DOCS and RC-C3DFOC
supports a general 0…10 V signal. This input is not connected to any function but only acts as
a read-out for the signal. To configure this option, parameter 81 is set to option 7, “0…10 V”.
Flow input
AI2 may be configured as a flow calculation input. A flow corresponding to 0 V and one
corresponding to 10 V is set, and the flow is then calculated linearly between these two end
points. To configure the flow calculation, Parameter 81 has the additional option 8, “Flow
calculation”.
The calculated flow value may be shown in the display by setting parameter 42 to option 9.