Installation Checklist
All packing materials and restraints have been removed from each cabinet.
Each cabinet in the UPS system is placed in its installed location.
All cabinets (except stand-alone cabinets) are bolted together.
A ground bond is installed between all cabinets that are bolted together.
All switch boards, conduits, and cables are properly routed to the UPS and auxiliary
cabinets.
Power cables are terminated on bypass terminals
on 460V systems, El
El 5
on all other systems).
Power cables are terminated on the
input breaker (El
on 460V systems,
on all other systems).
A ground conductor is properly installed.
N is used, no other N-G bonds exist downstream from the UPS.
Battery
cables
and harness are terminated on the
battery contactor E4 and
Internal battery cabinet connections have been completed (bus bars, plugs, etc.)
Air conditioning equipment is installed and operating correctly.
The area around the
UPS system is clean and dust free. (It is recommended
that:the UPS be installed on a sealed concrete pad on a seated concrete floor.)
Adequate workspace exists around the UPS and other cabinets.
Adequate lighting is
around all UPS equipment
A
o&t is
within 26 feet of the UPS equipment.
Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
The
wiring for each RMP is terminated inside the UPS cabinet.
(OPTIONAL)
The Remote Emergency Power Off (REPO) device is mounted in its installed location
and its wiring terminated inside the UPS cabinet. (OPTIONAL)
Summary alarms and/or building
are wired
(OPTIONAL)
A Relay interface Module (RIM) mounted in
installed location and its
is
terminated inside the UPS cabinet. (OPTIONAL)
A Remote
Disconnect control is mounted in its installed location and its wiring
is terminated inside the UPS and Battery Cabinet.
Plus UPS Installation
9
Summary of Contents for Plus 80
Page 1: ...0 Powerware Plus 80 Unintemqtibk Power Supply Operation 164200252 Rev A...
Page 55: ...a 1 a Pe WNP U N I N T E R R U P T I B L E P O W E R S Y S T E M S I i b I EXlDE ELECTRONICS...
Page 88: ...I I I I I I IO I I I I b I I NOTES 10 Powemam Plus 60 UPS ln stallation Manual...
Page 147: ...2 I FRONT Powerware Plus 80 UPS installation Manual A 13...
Page 153: ...5 61 CRE47Eo By L ORLANDO RMWON A ONE B 269r Powemare Plus 90 UPS lnstailation Manual A 19...