Function
Prog.
no.
Level
1)
Standard value
Buffer temp 2
8982
C
Buffer temp 3
8983
C
Relay output QX1
Off | On
9031
C
Relay output QX2
Off | On
9032
C
Relay output QX3
Off | On
9033
C
Relay output QX21 module 1
Off | On
9050
C
Relay output QX22 module 1
Off | On
9051
C
Relay output QX23 module 1
Off | On
9052
C
Relay output QX21 module 2
Off | On
9053
C
Relay output QX22 module 2
Off | On
9054
C
Relay output QX23 module 2
Off | On
9055
C
Relay output QX21 module 3
Off | On
9056
C
Relay output QX22 module 3
Off | On
9057
C
Relay output QX23 module 3
Off | On
9058
C
Burner control
Prepurge time
9500
F
20 s
Nominal output prepurging
9504
F
EC three 125: 59,3 kW
EC three 170: 75,5 kW
EC three 215: 77,1 kW
EC three 260: 97,7 kW
EC three 300: 103,9 kW
Nominal output ignition load
9512
F
EC three 125: 59,3 kW
EC three 170: 75,5 kW
EC three 215: 77,1 kW
EC three 260: 97,7 kW
EC three 300: 103,9 kW
Nominal output Partial load
9524
F
EC three 125: 20 kW
EC three 170: 28 kW
EC three 215: 35 kW
EC three 260: 42 kW
EC three 300: 48 kW
Nominal output full load
9529
F
EC three 125: 125 kW
EC three 170: 170 kW
EC three 215: 215 kW
EC three 260: 260 kW
EC three 300: 300 kW
Postpurge time
9540
F
20 s
Programming
76
Condensing gas boiler Eurocondense three125-300 kW
7308536-02 06.13