Function
Prog.
no.
Level
1)
Standard value
Flow temp setpoint max
741
E
80°C
Flow temp setpoint room stat
742
E
- - -°C
Delay heat request
746
E
0s
Room influence
750
C
- - - %
Room temp limitation
760
E
0.5°C
Boost heating
770
E
- - -°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
780
E
Down to reduced set-
point
Optimum start control max
790
E
0 min
Optimum stop control max
791
E
0 min
Reduced setp increase start
800
E
- - -°C
Reduced setp increase end
801
E
-15°C
Continuous pump operation
No | Yes
809
E
No
Overtemp prot pump circuit
Off | On
820
E
Off
Mixing valve boost
830
E
5°C
Actuator running time
834
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
850
C
Off
Floor curing setp manually
851
E
25°C
Floor curing setp current
855
E
- - -°C
Floor curing day current
856
E
0°C
Excess heat draw
Off | Heating mode | Always
861
E
Heating mode
With buffer storage tank
Off | Heating mode | Always
870
E
Yes
With prim contr/system pump
No | Yes
872
E
Yes
Pump speed reduction
Operating level | Characteristic
880
E
Characteristic
Pump speed min
882
C
10 %
Pump speed max
883
C
100 %
Curve readj at 50% speed
888
E
10 %
Flow setp readj speed ctrl
No | Yes
890
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
898
E
Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
900
E
Protection
Heating circuit 2
Parameter only visible, if heating circuit 2 exists!
Operating mode Heating circuit 2
Protection | Automatic | Reduced | Comfort
1000
Eu
Automatic
Programming
56
Condensing gas boiler Eurocondense three125-300 kW
7308536-02 06.13