Function
Prog.
no.
Level
1)
Standard value
Temp diff on
3810
C
8°C
Temp diff off
3811
C
4°C
Charg temp min DHW st tank
3812
I
- - - °C
Temp diff on buffer
3813
E
- - - °C
Temp diff off buffer
3814
E
- - - °C
Charging temp min buffer
3815
E
- - - °C
Temp diff on swi pool
3816
E
- - - °C
Temp diff off swi pool
3817
E
- - - °C
Charging temp min swi pool
3818
E
- - - °C
Charging prio storage tank
None | DHW storage tank | Buffer storage tank
3822
E
DHW storage tank
Charging time relative prio
3825
E
- - - min
Waiting time relative prio
3826
E
5 min
Waiting time parallel op
3827
E
- - - min
Delay secondary pump
3828
E
60 s
Collector start function
3830
E
- - -
Min run time collector pump
3831
E
20 s
Collector start function On
3832
E
07:00 (h:min)
Collector start function Off
3833
E
19:00 (h:min)
Collector start funct grad
3834
E
- - - min/°C
Collector frost protection
3840
E
- - - °C
Collector overtemp prot
3850
E
- - - °C
Evaporation heat carrier
3860
E
130°C
Antifreeze
None | Ethylene glycol | Propylene glycol | Ethyl and propyl glycol
3880
E
Propylene glycol
Antifreeze concentration
3881
E
50%
Pump capacity
3884
E
200 l/h
Pulse valency
3887
E
10 l
Solid fuel boiler
Locks other heat sources
Off | On
4102
E
Off
Setpoint min
4110
E
65°C
Temp diff on
4130
E
8°C
Temp diff off
4131
E
4°C
Comparative temp
DHW sensor B3 | DHW sensor B31 | Buffer sensor B4 | Buffer sensor
B41 | Flow temp setpoint | Setpoint min
4133
E
Buffer sensor B41
Pump overrun time
4140
E
20 min
Buffer storage tank
Auto heat gen lock
None | With B4 | With B4 and B42/B41
4720
E
With B4
Auto heat gen lock SD
4721
E
5°C
Temp diff buffer/HC
4722
E
-3°C
Min st tank temp heat mode
4724
E
- - - °C
Programming
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
63