Function
Prog. no.
Setting level
EC three 260
EC three 320
Natural
gas
LPG
Natural
gas
LPG
Fan output/speed slope
9626
E
21.5
19.9
19.9
19.0
Fan output/speed Y-section
9627
E
398.4
305.7
431.7
306.1
CO
2
content (± 0.2 %)
9.3
11.0
9.3
11.0
5.10 Controller Stop Mode
(Manual Adjustment of
Burner Load)
For setting and controlling the CO
2
values the EuroCondense three in operated in
the
control stop function
.
1.
> 3 s
xxxxxxxxxxxx
Press operation mode button Heating Operation for
approximately 3 seconds
=> the message
Controller Stop Function ON
is displayed.
2. Wait, until the display has reached the basic display again.
3.
Press information button
=> The message
Controller stop setpoint adjust
appears in the display. The ac-
tual modulation degree will be displayed on the display.
4. Press OK button
= > The nominal value can now be changed.
5. Press OK button
=> The displayed nominal value is taken over by the control.
Note:
The regulator stop function is stopped by pressing the
operating mode but-
ton Heating Operation
for approximately 3 seconds, reaching the maximum boiler
temperature or a time limit.
If a heat demand from a cylinder with internal indirect coil is present, this demand
will continue to be met while the controller stop function is running.
Installation
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
37