9.13 Fault code table
The following is the fault code table. In case of further displayed fault codes,
please inform the heating specialist.
Fault
code
Fault description
Explanations/causes
0
No error
10
Outside temp sensor fault
Connection or AT-sensor, emergency operation
20
Boiler temperature 1 Sensor fault
Check connection, inform heating specialist
1)
25
Boiler temperature solid fuel sensor fault
26
Boiler temperature solid fuel sensor fault
28
Boiler temperature solid fuel sensor fault
30
Flow temperature 1 Sensor fault
32
Flow temperature 2 Sensor fault
Check connection, inform heating specialist
1)
38
Boiler temperature solid fuel sensor fault
40
Return temperature 1 Sensor fault
Check connection, inform heating specialist
1)
46
Boiler temperature solid fuel sensor fault
47
Common return temp sensor fault
50
DHW temperature 1 sensor fault
Check connection, inform heating specialist, emergency
operation
1
52
DHW temperature 2 sensor fault
Check connection, inform heating specialist
1)
54
Flow temperature DHW sensor fault
57
Drinking water circulation temperature sensor
fault
60
Room temperature 1 sensor fault
65
Room temperature 2 sensor fault
68
Room temperature 3 sensor fault
70
Storage tank temp 1 (top) sensor fault
71
Storage tank temp 2 (bottom) sensor fault
72
Storage tank temp 3 (middle) sensor fault
73
Collector temperature 1 sensor fault
81
LPB short-circuit or no bus power supply
82
LPB Address collision
Check addresses of connected control modules
83
BSB-wire short/circuit
Check connection of the room units
84
BSB Address collision
2 room devices have the same allocation (Prog.-Nr. 42)
85
BSB-radio communication fault
91
EEPROM fault: information of locking mechanism Internal fault LMS, process sensor, replace LMS, heating
specialist
98
Expansion module 1 fault (collective fault)
99
Expansion module 2 fault (collective fault)
100
Two time masters (LPB)
Check time master
102
Clock time master without backup
105
Servicing message
See maintenance code (press information button once)
for detailed information
109
Boiler temperature monitoring
Maintenance