9.8 Electrode spacing and
installation locations
Fig. 38: Electrode spacing and installation locations
4 mm
1
2
8 mm
8 mm
1 Ionisation electrode
2 Ignition electrode block
9.9 Clean burner pipe
1. Removing burner (see section
Installing and removing burner
)
Fig. 39: Dismantle burner pipe
C0004611
1
2
2. Remove screws and remove burner pipe (1) with the burner pipe seal (2)
3. Clean the burner pipe with compressed air
4. Reinstall burner pipe with burner pipe seal
Note: Use a new burner pipe seal when installing the burner pipe.
5. Reinstall burner (see section
Installing and removing burner
)
Maintenance
136
Condensing gas boiler Eurocondense three125-300 kW
7308536-02 06.13