Function
Prog.
no.
Level
1)
Standard value
Flow setp readj speed ctrl
No | Yes
1190
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
1198
E
Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
1200
E
Protection
Heating circuit 3
Parameter only visible, if heating circuit 3 exists!
Operating mode Heating circuit 3
Protection | Automatic | Reduced | Comfort
1300
Eu
Automatic
Comfort setpoint
1310
Eu
20.0°C
Reduced setpoint
1312
Eu
18.0°C
Frost protection setpoint
1314
Eu
10.0°C
Heating curve slope
1320
Eu
1.50
Heating curve displacement
1321
E
0.0°C
Heating curve adaption
Off | On
1326
E
Off
Summer/winter heating limit
1330
Eu
20°C
24-hour heating limit
1332
E
- 0°C
Flow temp setpoint min
1340
E
8°C
Flow temp setpoint max
1341
E
80°C
Flow temp setpoint room stat
1342
E
- - -°C
Delay heat request
1346
E
0s
Room influence
1350
C
- - - %
Room temp limitation
1360
E
0.5°C
Boost heating
1370
E
- - -°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
1380
E
Down to reduced set-
point
Optimum start control max
1390
E
0 min
Optimum stop control max
1391
E
0 min
Reduced setp increase start
1400
E
- - -°C
Reduced setp increase end
1401
E
-15°C
Continuous pump operation
No | Yes
1409
E
No
Overtemp prot pump circuit
Off | On
1420
E
Off
Mixing valve boost
1430
E
5°C
Actuator running time
1434
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
1450
E
Off
Floor curing setp manually
1451
E
25°C
Floor curing setp current
1455
E
- - -°C
Floor curing day current
1456
E
0°C
Programming
58
Condensing gas boiler Eurocondense three125-300 kW
7308536-02 06.13