Function
Prog.
no.
Level
1)
Standard value
Excess heat draw
Off | Heating mode | Always
1461
E
Heating mode
With buffer storage tank
No | Yes
1470
E
Yes
With prim contr/system pump
No | Yes
1472
E
Yes
Pump speed reduction
Operating level | Characteristic
1480
E
Characteristic
Pump speed min
1482
C
10 %
Pump speed max
1483
C
100 %
Curve readj at 50% speed
1488
E
10 %
Flow setp readj speed ctrl
No | Yes
1490
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
1498
E
Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
1500
E
Protection
DHW
Nominal setpoint
1610
Eu
55°C
Reduced setpoint
1612
E
45°C
Release
24h/day | Time programmes HCs | Time programme 4/DHW
1620
Eu
Time program 4/DHW
Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
1630
E
MC shifting, PC absolute
Legionella function
Off | Periodically | Fixed weekday
1640
E
Fixed weekday
Legionella funct periodically
1641
E
3
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday | Saturday | Sun-
day
1642
E
Sunday
Legionella funct time
1644
E
- - -
Legionella funct setpoint
1645
E
65°C
Legionella funct duration
1646
E
- - - min
Legionella function circ pump
Off | On
1647
E
On
Circulating pump release
Time programme 3 / HCP | DHW release | Time programme 4/DHW |
Time program 5
1660
C
DHW release
Circulating pump cycling
Off | On
1661
C
On
Circulation setpoint
1663
E
55°C
Optg mode changeover
None | Off | On
1680
E
Off
Consumer circuit 1
Flow temp setp cons request
1859
C
70°C
DHW charging priority
- No | Yes
1874
E
Yes
Programming
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW