64
ID-E270-011GB
Table 7.5
Variant
Control
Panel
No.
Zone
Number
Actuation criterion
0
―
―
Inactive output
1
0
―
1
st
stage general alarm
2
0 ÷ 31
0 ÷ 1024
‘union’ of 1
st
stage alarms in assigned zones
3
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 1
st
stage alarms in assigned zones
4
0
―
2
nd
stage general alarm
5
0 ÷ 31
0 ÷ 1024
‘union’ of 2
nd
stage alarms in assigned zones
6
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 2
nd
stage alarms in assigned zones
Variant 0
Means lack of the relay actuation criterion (permanently non-activated output).
Variant 1 – general 1
st
stage alarm
The output activation is performed in the case of a 1
st
stage alarm occurrence in the control panel or
any control panel of the common supervision area.
Variant 2 – ‘union’ of 1
st
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 1
st
stage alarm occurrence in at least one zone
that is assigned to this relay.
Variant 3 – ‘conjunction’ of 1
st
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a 1
st
stage alarm occurrence in at least two zones
that are assigned to this relay.
Variant 4 – general 2
nd
stage alarm
The output activation is performed in the case of a 2
nd
stage alarm occurrence in the control panel or
any control panel of the common supervision area.
Variant 5 – ‘union’ of 2
nd
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least one zone
that is assigned to this relay.
Variant 6 – ‘conjunction’ of 2
nd
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least two zones
that are assigned to this relay.