The program makes it possible to provide each zone with a text message (user message) containing
two lines of text and max. 32 characters in each line.
In the case an alarm is received from a zone, this text is displayed on the LCD screen showing the
precise location of the fire.
7.2 ADDRESSABLE ELEMENTS DECLARATION
The control panel receives information and controls the operation of addressable elements which
have been declared (assigned to operation) by the user. The control panel is delivered with the
standard configuration loaded in which no addressable element is declared. Until the elements are
declared, the control panel does not receive signals regarding line elements type and status but,
every 2 minutes, it checks the compliance of the elements installed in the addressable detection line
with the declared ones and, in case an irregularity is detected, a fault, whose type can be read, is
indicated.
An addressable element declaration consists in defining the element following data:
-
line number;
-
element number;
and providing the following data for this address:
-
serial number (entered manually or using a bar code reader);
-
zone number and logical number;
-
zone number (from the 1 ÷ 1024 range) in the case of manual call points;
-
logical number (1 ÷ 250 range) for the EKS-4001 monitoring and controlling elements and for
the SAL-4001 addressable signalling devices;
-
logical number (1 ÷ 100 range) for the EWS-4001, EWK-4001 UCS 4000, UCS 6000 line
elements;
-
A or B group (within a given zone) for manual call points;
-
operation mode (according to individual possibilities and needs for different element types).
The addressable elements declaration can be preceded by automatic configuration or configuration
with verification that enable matching consecutive element numbers with their factory numbers.
Incorrect type assignment to an addressable element is revealed by the control panel and indicated
as a fault.
Note:
1. Any number of warning devices can be installed in one detection line. It is recommended,
however, to install not more than 32 warning devices.
2. Line elements logical numbers can repeat only in the case of different element types, e.g. the
logical number 35 can be assigned simultaneously to one element of a device group: EKS, EWK, EWS,
SAL or UCS.
7.3 ASSIGNING ALARMING PARAMETERS TO ZONES
In order to group addressable elements, installed in the supervised premises, the territory is divided
into zones (separated parts of the premises, room, etc.). In the POLON 4900 control panel it is
possible to create up to 1024 detection zones. Every zone can be described with the user message
composed of two text lines up to 32 characters each.
Zone creation means assigning an addressable element with a short number to the zone number,
according to the PM.
The POLON 4900 control panel ensures a possibility to choose an alarm method for a particular zone,
one of the 14 available ones.