54
ID-E270-011GB
-
the output is activated in case a non-maskable fault is revealed in at least one assigned input
from the list of assigned EKS elements. The assigned inputs may not include own inputs of
the controlled EKS element. The list of assigned EKS inputs may include only their own
control panel (when the control panel operates in a network).
Variant 12 – ‘union’ of technical alarms in assigned EKS inputs
-
the output is activated in case a technical alarm is generated in at least one assigned input
from the list of assigned EKS elements. The assigned inputs may include own inputs of the
controlled EKS element. The list of assigned EKS inputs may include only their own control
panel (when the control panel operates in a network).
Variant 13 – ‘union’ of faults in assigned EWK inputs
-
the output is activated in case a fault is revealed in at least one assigned input from the list of
assigned EWK elements. The list of assigned EWK inputs may include only their own control
panel (when the control panel operates in a network).
Variant 14 – ‘union’ of technical alarms in assigned EWK inputs
-
the output is activated in case a technical alarm is generated in at least one assigned input
from the list of assigned EWK elements. The list of assigned EWK inputs may include only
their own control panel (when the control panel operates in a network).
Variant 15 – reset output
-
the reset output's objective is to generate a reset impulse (duration approx. 1.5 second),
after a fire alarm is reset. This type may be used, e.g. to supply or reset detectors requiring a
separate power supply, e.g. flame detectors manufactured by Det-Tronics.
Variant 16 – alarm device - general 1
st
stage alarm
-
in this variant, an output is treated in the system as an alarm device.
The output is activated in case a 1
st
stage alarm is generated in the control panel or in any
control panel from the common detection area.
Variant 17 – alarm device – ‘union’ of 1
st
stage alarms in assigned zones
-
in this variant, an output is treated in the system as an alarm device.
The output is activated when a 1
st
stage alarm is generated in at least one of the zones
assigned to this relay.
The output relay actuation variants are programmed only for an EKS element with a logical number
defined.
In case variant 2 or 5 is used, at least one zone must be assigned to the EKS element, however, if
variant 3 or 6 is used, at least two zones must be assigned. Variants 1 and 4 do not require
assigning any zones.
As far as the variants with zone dependence are concerned, the assigned zones may originate in
their own control panel (a standalone control panel) or in any control panels from the common
detection area (a control panel operating in a network).
The total number of zones, EKS and EWK elements assigned to all executive outputs and SAL type
elements in the control panel must not exceed 64,000.
Note:
-
A non-maskable fault of an output may occur only during the output actuation monitoring
time. For example, for the Yes (40 sec.) mode, if a technical alarm mode occurred during 40
seconds from output actuation and the line resistance changed into the resistance equivalent
to a non-maskable fault, a non-maskable fault will not be signalled.