12
ID-E270-011GB
Liquid Cristal Display (graphical) - resolution:
Time programming ranges:
-
T1 time - waiting for confirmation of a 1
st
STAGE ALARM
-
T2 time - situation recognition after a 1
st
STAGE ALARM confirmation
-
T3 time - alarm outputs activation delay
Programmable outputs (PK1 constantly programmed):
-
1 A/24 V relay non-potential switchable contacts
-
signalling lines of 0.5 A/24 V capacity
-
signalling lines of 100 mA / 24 V capacity
Programmable inputs – monitoring lines:
number of monitoring lines
monitoring line resistance
Maximum number of zones/controlling elements assigned to outputs (total number of
assignments to PK and LS type outputs and EKS-4001, EWS-4001, UCS 4000 and UCS
6000 type line elements)
Maximum number of stored events (EVENT MEMORY)
Maximum number of stored alarms (ALARM MEMORY)
Control panel case ingress protection degree
Operating temperature range
Control panel mass (without batteries)
Control panel dimensions (without PAR-4800 container)
PAR-4800 battery container dimensions
Control panel dimensions with PAR-4800 container attached
Interoperation with devices:
-
bar code reader,
-
computer keyboard,
-
computer,
-
TELSAP 2100 digital monitoring system,
-
POLON 4000 (PMC-4000) digital monitoring system,
-
control panels framework interoperation – max. number of control panels
-
control panel co-operation with the TSR-4000 terminals – maximum
number of terminals connected to one control panel
320 x 240 pixels
0 ÷ 10 min
0 ÷ 10 min
0 ÷ 10 min
16 (PK1 ÷ PK16)
2 (LS1, LS2)
6 (LS3÷LS8)
8 (LK1÷LK8)
see Table 5.9
64,000
2,000
9,999
IP30
- 5
o
C ÷ + 40
o
C
ca. 17 kg
536x492x218 mm
212x492x195 mm
766x492x218 mm
31
16